ABB Relion 670 Series Technical Reference Manual page 567

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
9.2.5
Table 291:
SAPTOF (81) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
VBase
0.05 - 2000.00
PUFrequency
35.00 - 75.00
IntBlockLevel
0 - 100
TimeDlyOperate
0.000 - 60.000
TimeDlyReset
0.000 - 60.000
9.2.6
9.3
Technical reference manual
Table 290:
SAPTOF (81) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
BLKDMAGN
BOOLEAN
FREQ
REAL
Setting parameters
Unit
Step
-
-
kV
0.05
Hz
0.01
%VB
1
s
0.001
s
0.001
Technical data
Table 292:
SAPTOF (81) technical data
Function
Operate value, pickup function
Operate time, pickup function
Reset time, pickup function
Operate time, definite time
function
Reset time, definite time function
Rate-of-change frequency protection SAPFRC (81)
Description
Operate/trip signal for frequency.
Start/pick-up signal for frequency.
Blocking indication due to low magnitude.
Measured frequency
Default
Description
Disabled
Disable/Enable Operation
400.00
Base voltage
51.20
Frequency setting pickup value.
50
Internal blocking level in % of VBase.
0.000
Operate time delay in over/under-frequency
mode.
0.000
Time delay for reset.
Range or value
(35.00-75.00) Hz
100 ms typically at f
-0.5 Hz to f
set
100 ms typically
(0.000-60.000)s
(0.000-60.000)s
Section 9
Frequency protection
Accuracy
± 2.0 mHz at
symmetrical three-
phase voltage
+0.5 Hz
-
set
-
± 0.5% ± 10 ms
± 0.5% ± 10 ms
561