ABB Relion 670 Series Technical Reference Manual page 993

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
16.1.5
Table 605:
PCGGIO Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
EventMask
NoEvents
ReportEvents
CountCriteria
Disabled
RisingEdge
Falling edge
OnChange
Scale
1.000 - 90000.000
Quantity
Count
ActivePower
ApparentPower
ReactivePower
ActiveEnergy
ApparentEnergy
ReactiveEnergy
tReporting
0 - 3600
16.1.6
16.2
Technical reference manual
Setting parameters
Unit
Step
-
-
-
-
-
-
-
0.001
-
-
s
1
Technical data
Table 606:
PCGGIO technical data
Function
Input frequency
Cycle time for report of
counter value
Function for energy calculation and demand handling
ETPMMTR
Function description
Energy calculation and demand
handling
Default
Description
Disabled
Operation Enable/Disable
NoEvents
Report mask for analog events from pulse
counter
RisingEdge
Pulse counter criteria
1.000
Scaling value for SCAL_VAL output to unit
per counted value
Count
Measured quantity for SCAL_VAL output
60
Cycle time for reporting of counter value
Setting range
See Binary Input Module (BIM)
(1–3600) s
IEC 61850
IEC 60617
identification
identification
ETPMMTR
Section 16
Metering
Accuracy
-
-
ANSI/IEEE C37.2
device number
-
987