Advertisement

1MRK505222-UUS C
5.3.5
Table 90:
STSGGIO (11REL) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
tStUpReset
0.000 - 60.000
Enable CV
Disabled
Enabled
Pick Up ICV
1 - 100
Operation37
Disabled
Enabled
PU_37
0 - 100
Enable 3I0
Disabled
Enabled
PU 3I0
1 - 100
OperationUV
Disabled
Enabled
V_Ph-N
1 - 100
V_Ph-Ph
1 - 100
Table 91:
STSGGIO (11REL) Group settings (advanced)
Name
Values (Range)
Time Delay CV
0.000 - 0.005
tUC
0.000 - 60.000
t3I0
0.000 - 60.000
tUV
0.000 - 60.000
HysAbsUV
0.0 - 100.0
Technical reference manual

Setting parameters

Unit
Step
-
-
A
1
kV
0.05
s
0.001
-
-
%IB
1
-
-
%IB
1
-
-
%IB
1
-
-
%VB
1
%VB
1
Unit
Step
s
0.001
s
0.001
s
0.001
s
0.001
%VB
0.1
Default
Description
Disabled
Operation Off/On
3000
Base setting for current in A
400
Base setting for voltage in kV
7.000
Reset delay for startup signal
Enabled
Disable/Enable current variation operation
20
Fixed threshold for ph to ph current variation
criterion
Enabled
Disable/Enable low current criterion
5
Pickup for low current in % of IBase
Enabled
Disable/Enable zero sequence current
criterion
10
Pickup zero sequence current criterion in %
of IBase
Enabled
Disable/Enable under voltage criterion
60
Pickup phase voltage criterion in % of VBase
60
Pickup ph to ph voltage criterion in % of VBase
Default
Description
0.002
Time delay for phase to phase current variation
0.200
Time delay for low current criterion
0.000
Time delay for zero sequence current criterion
0.000
Time delay for low voltage criterion
0.5
Hysteresis absolute value for low voltage
criterion in % of UBase
Section 5
Differential protection
171