Table 383:
SLGGIO Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
NrPos
2 - 32
OutType
Pulsed
Steady
tPulse
0.000 - 60.000
tDelay
0.000 - 60000.000
StopAtExtremes
Disabled
Enabled
12.6
12.6.1
12.6.2
760
Setting parameters
Unit
Step
-
-
-
1
-
-
s
0.001
s
0.010
-
-
Selector mini switch VSGGIO
Function description
Selector mini switch
Introduction
The Selector mini switch VSGGIO function block is a multipurpose function used for a
variety of applications, as a general purpose switch.
VSGGIO can be controlled from the menu or from a symbol on the single line diagram
(SLD) on the local HMI.
Principle of operation
Selector mini switch (VSGGIO) function can be used for double purpose, in the same
way as switch controller (SCSWI) functions are used:
for indication on the single line diagram (SLD). Position is received through the
IPOS1 and IPOS2 inputs and distributed in the configuration through the POS1
and POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
for commands that are received via the local HMI or IEC 61850 and distributed in
the configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command
from the local HMI when the SLD is displayed and the object is chosen.
Default
Description
Disabled
Operation Enable/Disable
32
Number of positions in the switch
Steady
Output type, steady or pulse
0.200
Operate pulse duration, in [s]
0.000
Time delay on the output, in [s]
Disabled
Stop when min or max position is reached
IEC 61850
IEC 60617
identification
identification
VSGGIO
-
1MRK505222-UUS C
ANSI/IEEE C37.2
device number
-
Technical reference manual