Section 5
Differential protection
146
Name
Type
IDMAG_A
REAL
IDMAG_B
REAL
IDMAG_C
REAL
IBIAS
REAL
IDMAG_NS
REAL
Table 62:
L6CPDIF (87L) Input signals
Name
Type
I3P1
GROUP
SIGNAL
I3P2
GROUP
SIGNAL
I3P3
GROUP
SIGNAL
I3P4
GROUP
SIGNAL
I3P5
GROUP
SIGNAL
I3P6
GROUP
SIGNAL
Table 63:
L6CPDIF (87L) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
TRIPRES
BOOLEAN
TRIPUNRE
BOOLEAN
TRIPENHA
BOOLEAN
PICKUP
BOOLEAN
PU_A
BOOLEAN
PU_B
BOOLEAN
PU_C
BOOLEAN
BLK2H
BOOLEAN
BLK2H_A
BOOLEAN
BLK2H_B
BOOLEAN
Table continues on next page
Description
Magnitude of fund. freq. differential current, phase A
Magnitude of fund. freq. differential current, phase B
Magnitude of fund. freq. differential current, phase C
Magnitude of the bias current, common for phase A,B.C
Magnitude of the negative sequence differential current
Default
Description
-
Three phase current grp1 samples and DFT values
-
Three phase current grp1 samples and DFT values
-
Three phase current grp1 samples and DFT values
-
Three phase current grp1 samples and DFT values
-
Three phase current grp1 samples and DFT values
-
Three phase current grp1 samples and DFT values
Description
Main Trip Signal
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
Trip by restrained differential 87L
Trip by unrestrained differential 87H
Trip by Enhanced restrainted differential 87LEnhanced
Main Pickup output signal
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
Block signal due to second harmonic
Block signal due to second harmonic phase A
Block signal due to second harmonic phase B
1MRK505222-UUS C
Technical reference manual