ABB Relion 670 Series Technical Reference Manual page 605

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
11.1.3
11.1.4
Technical reference manual
| åI
| - | I
|
phase
ref
I
MinOp
IEC99000068 V1 EN
Figure 301:
Operate characteristics
Due to the formulas for the axis compared, |SIphase | - |I ref | and |S I
phase | + | I ref | respectively, the slope can not be above 2.
Function block
CCSRDIF (87)
I3P*
FAIL
IREF*
ALARM
BLOCK
ANSI05000389-2-en.vsd
ANSI05000389 V2 EN
Figure 302:
CCSRDIF (87) function block
Input and output signals
Table 306:
CCSRDIF (87) Input signals
Name
Type
I3P
GROUP
SIGNAL
IREF
GROUP
SIGNAL
BLOCK
BOOLEAN
Secondary system supervision
Slope = 1
Operation
Slope = 0.8
| åI
phase
Default
Description
-
Group signal for three phase current input
-
Reference current signal input
0
Block of function
Section 11
area
| + | I
|
ref
99000068.vsd
599