Section 6
Impedance protection
6.5.2
6.5.2.1
262
X
Reverse
operation
IEC05000034 V1 EN
Figure 130:
Typical quadrilateral distance protection zone with Phase selection,
quadrilateral characteristic with settable angle function FRPSPDIS (21)
activated
The independent measurement of impedance for each fault loop together with a
sensitive and reliable built in phase selection makes the function suitable in
applications with single phase auto-reclosing.
Built-in adaptive load compensation algorithm prevents overreaching of zone1 at load
exporting end at phase to ground faults on heavily loaded power lines.
The distance protection zones can operate, independent of each other, in directional
(forward or reverse) or non-directional mode. This makes them suitable, together with
different communication schemes, for the protection of power lines and cables in
complex network configurations, such as parallel lines, multi-terminal lines.

Principle of operation

Full scheme measurement

The different fault loops within the IED are operating in parallel in the same principle
as a full scheme measurement.
Figure
131
presents an outline of the different measuring loops for the basic five,
impedance-measuring zones l.
Forward
operation
R
en05000034.vsd
1MRK505222-UUS C
Technical reference manual