ABB Relion 670 Series Technical Reference Manual page 923

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Name
Values (Range)
IB_RepTyp
Cyclic
Dead band
Int deadband
IB_AngDbRepInt
1 - 300
IC_DbRepInt
1 - 300
IC_Max
0.000 -
10000000000.000
IC_RepTyp
Cyclic
Dead band
Int deadband
IC_AngDbRepInt
1 - 300
Table 555:
CMMXU Non group settings (advanced)
Name
Values (Range)
IA_ZeroDb
0 - 100000
IA_HiHiLim
0.000 -
10000000000.000
IA_HiLim
0.000 -
10000000000.000
IMagComp5
-10.000 - 10.000
IMagComp30
-10.000 - 10.000
IA_LowLim
0.000 -
10000000000.000
IA_LowLowLim
0.000 -
10000000000.000
IMagComp100
-10.000 - 10.000
IAngComp5
-10.000 - 10.000
IA_Min
0.000 -
10000000000.000
IAngComp30
-10.000 - 10.000
IAngComp100
-10.000 - 10.000
IA_LimHys
0.000 - 100.000
IB_ZeroDb
0 - 100000
IB_HiHiLim
0.000 -
10000000000.000
Table continues on next page
Technical reference manual
Unit
Step
Default
-
-
Cyclic
Type
1
10
Type
1
10
A
0.001
1000.000
-
-
Cyclic
Type
1
10
Unit
Step
Default
m%
1
0
A
0.001
900.000
A
0.001
800.000
%
0.001
0.000
%
0.001
0.000
A
0.001
0.000
A
0.001
0.000
%
0.001
0.000
Deg
0.001
0.000
A
0.001
0.000
Deg
0.001
0.000
Deg
0.001
0.000
%
0.001
5.000
m%
1
0
A
0.001
900.000
Section 15
Monitoring
Description
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Description
Zero point clamping in 0.001% of range
High High limit (physical value)
High limit (physical value)
Magnitude factor to calibrate current at 5% of
In
Magnitude factor to calibrate current at 30%
of In
Low limit (physical value)
Low Low limit (physical value)
Magnitude factor to calibrate current at 100%
of In
Angle calibration for current at 5% of In
Minimum value
Angle calibration for current at 30% of In
Angle calibration for current at 100% of In
Hysteresis value in % of range and is
common for all limits
Zero point clamping in 0.001% of range
High High limit (physical value)
917

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670

Table of Contents