Appendix C — Specifications
Power Specifications
This section describes the power specifications for the library. For
information about the different types of AC power modules, see Dual AC 2
Power Module on page 37.
Input Power Requirements
The main frame and drive expansion frames include dual AC power
modules. When using a redundant power configuration, connect each
input on the dual AC power module to a separate branch circuit, which
allows for failover in the event of a power failure in one of the circuits.
Each library frame is rated at 200 – 2 40 VAC at 13 amps (2600 watts
maximum). This power rating is based on a main frame with 24 LTO drives
and 6 RIMs, which is the configuration for maximum power consumption
by a single frame. The frames are not rated at 120 VAC due to the high
current required to supply the product.
Power Cord Specifications
The power cords included with the library are considered part of the
library and are not intended for use with any other equipment. See Supply‐
End Connector Types on page 482 for the different types of cords available
from Spectra Logic.
North America and Korea 200 – 240 VAC Power Cord The criteria for a
200‐volt to 240‐volt AC power cord in North America and Korea are as
follows:
August 2019
The supply‐end connector is considered the disconnect for
Notes:
the unit. Make sure that the socket‐outlet for the AC
connection is in an accessible location near the library.
The power cord must meet the specifications for the country
where the library is to be installed.
Parameter
Power cordage
Power input connectors
Specification
SJT type, three‐conductor, 14 AWG minimum
Male: Connector must be of the proper type,
rating, and safety approval (see Supply‐End
Connector Types on page 482).
Female: IEC 60320 C19
User Guide—Spectra T950V Library
Library Specifications
481