Spectra Logic Spectra T950V User Manual page 483

Tape library
Hide thumbs Also See for Spectra T950V:
Table of Contents

Advertisement

Appendix C — Specifications
Grounding Requirements
Due to electromagnetic interference (EMI) filtering in each dual AC power 
supply, the leakage current for main frames and drive frames is such that 
they require a secure connection from the frame chassis to an earth ground. 
Use one of the following methods for securing a ground connection when 
installing a main frame or drive frame:
 Add cord lock brackets (Spectra Logic part number 5497) to all drive 
 Use a cord with locking connectors at both ends, such as L6 20P to 
Power Consumption and Cooling Requirements
The power and cooling requirements for the library depend on the number 
and type of drives installed. The following table provides the maximum 
power consumption and heat load for the base library and for each 
additional component added to the base library. Use this information to 
calculate the total maximum power consumption and heat load values, 
which can be used to build a power budget for the library.
All values are measured at the AC input and include power supply 
efficiency. The values are averages of observed hardware. In general, the 
lighter the load on the power supplies, the less efficient they are. The 
power supply efficiency in turn affects the power draw of all components.
August 2019
Note:
Cord lock brackets and cords with locking connectors are not 
compatible and cannot be used simultaneously. 
frames. See Installing Cord Locks on page 412 for more information.
locking C19 (Spectra Logic part number 9594). 
Component
a
Main frame
a
Drive frame
Media frame without fan
5/12 VDC power supply
24 VDC power supply
RIM2
LTO-8 Fibre Channel
Full-Height
LTO-8 Fibre Channel or
SAS Half-Height
LTO-7 Fibre Channel
Full-Height
Power Consumption
(watts)
183
139
14
33
29
12
 Read/write: 40
b
 Idle: 15 
 Read/write: 43
b
 Idle: 14 
 Read/write: 31
b
 Idle: 20 
User Guide—Spectra T950V Library
Library Specifications
Heat Load, Continuous
(BTU/hour)
625
475
48
113
99
41
Read/write: 136
Read/write: 164
Read/write: 106
483