Appendix C — Specifications
a. Assumes one 5/12 volt power supply and one 24 volt power supply; no drives or RIM2s installed.
b. No cartridge loaded.
Environmental Specifications
This section describes environmental specifications for the library. Do not
place the library on a carpeted floor or anywhere else that poses risk for
static discharge that could damage the library and its drives.
The library must be installed on a level, hard-surfaced floor such as cement or tile.
Caution
Never install it on carpeted flooring.
The library is equipped with internal fans that operate as much as is
necessary for the number of DBAs installed. The fans keep the library's
internal temperature within specifications as long as the data center
environment is within specifications.
When the library is moved from a cold environment to a warm environment, it
Caution
should not be powered on for at least 24 hours. This adjustment period prevents
condensation damage.
August 2019
Component
LTO-7 Fibre Channel or
SAS Half-Height
LTO-6 Fibre Channel
TS1160 technology
TS1155 technology
TS1150 technology
Power Consumption
(watts)
Read/write: 36
b
Idle: 20
Read/write: 28
b
Idle: 8
Read/write: 67
b
Idle: 35
Read/write: 60
b
Idle: 19
Read/write: 55
b
Idle: 38
User Guide—Spectra T950V Library
Library Specifications
Heat Load, Continuous
(BTU/hour)
Read/write: 123
Read/write: 95
Read/write: 229
Read/write: 205
Read/write: 188
484