Chapter 13 — Drive Troubleshooting
4. Click Global Spare for the partition that contains the failed drive to 
5. Click Use Spare next to the drive for which you want to substitute an 
August 2019
display the Global Spare Usage screen.
The Global Spare button is not present if one or more drives are 
Note:
not configured as Global Spares for the partition (see Assign 
Global Spare Drives on page 176).
Figure 199 Click Use Spare for the drive you want to replace.
available Global Spare drive. Wait for the library to complete the 
sparing operation. 
 When you select the drive to replace, the BlueScale software 
Notes:
disables the selected drive and configures an available Global 
Spare drive to report the same WWN and serial number as 
the drive it is replacing. The failed drive can then be removed 
and replaced the next time you are physically at the library.
 If you have more than one available Global Spare drive, the 
library automatically selects a drive in no particular order.
Using a Global Spare Drive
User Guide—Spectra T950V Library