Cli-Console-Timeout - Siemens SIMATIC NET Configuration Manual

Industrial wireless lan to ieee 802.11n command line interface
Hide thumbs Also See for SIMATIC NET:
Table of Contents

Advertisement

Further notes
You configure an interface with the
You display the status and the configuration of the interfaces with the
command.
3.1.9.7

cli-console-timeout

Description
With this command, you enable the automatic logout and you configure the timeout setting
for the CLI.
Note
No automatic logout from the CLI
If the connection is not terminated after the set time, check the setting of the "keepalive"
function on the Telnet client. If the set interval is shorter than the configured time, the lower
value applies. You have set, for example, 300 seconds for the automatic logout and 120
seconds for the "keepalive" function. In this case, a packet is sent every 120 seconds that
keeps the connection up.
Requirement
You are in the Global configuration mode.
The command prompt is as follows:
cli(config)#
Syntax
Call up the command with the following parameters:
cli-console-timeout [seconds(60-600)]
The parameters have the following meaning:
Parameter
seconds
Result
The time is configured and automatic logout is enabled.
Further notes
You disable automatic logout with the
You display the current timeout setting with the
SCALANCE W760/W720 to IEEE 802.11n Command Line Interface
Configuration Manual, 10/2015, C79000-G8976-C351-05
command.
interface
Description
Time in seconds until automatic logout
after the last entry
no cli-console-timeout
show interfaces
Range of values / note
60 ... 600
Default: 300
command.
show cli-console-timeout
Configuration
3.1 System
command.
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scalance w720Scalance w760

Table of Contents