Siemens SIMATIC NET Installation Manual

Siemens SIMATIC NET Installation Manual

Rugged ethernet switches
Hide thumbs Also See for SIMATIC NET:

Advertisement

Quick Links

Installation Manual
SIMATIC NET
Rugged Ethernet Switches
RUGGEDCOM RP100
Edition
01/2021
https://www.siemens.com

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC NET

  • Page 1 Installation Manual SIMATIC NET Rugged Ethernet Switches RUGGEDCOM RP100 Edition 01/2021 https://www.siemens.com...
  • Page 2 Preface Introduction Installing the Device SIMATIC NET Device Management Rugged Ethernet Switches RUGGEDCOM RP100 Communication Ports Technical Specifications Installation Manual Certification 01/2021 C79000-G8976-1011-05...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Table Of Contents

    Accessing Documentation ....................... v Registered Trademarks ......................v Warranty ..........................v Training ..........................vi Customer Support ........................vi Contacting Siemens ........................ vi Introduction ........................... 1 Description ......................2 Required Tools and Materials ................. 3 Decommissioning and Disposal ................3 Installing the Device ......................5 General Procedure ....................
  • Page 5 Table of Contents 6.1.6 ACMA ........................21 6.1.7 RoHS ........................21 EMC and Environmental Type Tests ..............21 RUGGEDCOM RP100 Installation Manual, 01/2021, C79000-G8976-1011-05...
  • Page 6: Preface

    Warranty Siemens warrants this product for a period of five (5) years from the date of purchase, conditional upon the return to factory for maintenance during the warranty term. This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void.
  • Page 7: Training

    Siemens Sales representative. Customer Support Customer support is available 24 hours, 7 days a week for all Siemens customers. For technical support or general information, contact Siemens Customer Support through any of the following methods: Online Visit http://www.siemens.com/automation/support-request...
  • Page 8 Preface Contacting Siemens 300 Applewood Crescent Concord, Ontario Canada, L4K 5C7 Telephone Toll-free: 1 888 264 0006 Tel: +1 905 856 5288 Fax: +1 905 856 1995 E-Mail ruggedcom.info.i-ia@siemens.com https://www.siemens.com RUGGEDCOM RP100 Installation Manual, 01/2021, C79000-G8976-1011-05...
  • Page 9 Preface Contacting Siemens viii RUGGEDCOM RP100 Installation Manual, 01/2021, C79000-G8976-1011-05...
  • Page 10: Introduction

    Introduction The RUGGEDCOM RP100 provides the flexibility to power remote PoE (Power over Ethernet) devices using standard shielded CAT 5 cables. Converging data and power onto a single cable saves money, space and labor for new and existing installations. Compatible with the latest 802.3at high power PoE standard and backwards compatible with low power 802.3af PoE devices, the RP100 provides versatility and investment protection to handle future demands for increased power.
  • Page 11: Description

    Introduction 1.1 Description Key Features • Substation Rated: • IEC 61850-3 • IEEE 1613 • -40 to 85 °C (-40 to 185 °F) operating (no fans) • Industrial Design: • Panel or DIN mounting • Lightweight Cast Aluminum Enclosure • Performance: •...
  • Page 12: Required Tools And Materials

    Introduction 1.2 Required Tools and Materials Power Supply Terminal Block A pluggable terminal block. For more information, refer to "Connecting Power (Page 10)" "Power Supply Specifications (Page 17)" POWER LED Illuminates when power is being supplied to the device. Copper Ethernet Ports Receive and transmit data, as well as provide power to a RUGGEDCOM WIN subscriber station.
  • Page 13 Introduction 1.3 Decommissioning and Disposal RUGGEDCOM RP100 Installation Manual, 01/2021, C79000-G8976-1011-05...
  • Page 14: Installing The Device

    This product contains no user-serviceable parts. Attempted service by unauthorized personnel shall render all warranties null and void. Changes or modifications not expressly approved by Siemens AG could invalidate specifications, test results, and agency approvals, and void the user's authority to operate the equipment.
  • Page 15: Unpacking The Device

    Visually inspect each item in the package for any physical damage. Verify all items are included. IMPORTANT If any item is missing or damaged, contact Siemens for assistance. Mounting the Device The RUGGEDCOM RP100 can be ordered with a DIN rail adapter pre-installed on the back of the chassis.
  • Page 16 Installing the Device 2.3 Mounting the Device Note For detailed dimensions of the device with the DIN rail adapter installed, refer to "Dimension Drawings (Page 18)". Mounting the Device To mount the device to a DIN rail, do the following: Hook the top teeth of the adapter onto the DIN rail. DIN Rail DIN Rail Adapter Figure 2.1...
  • Page 17: Installing The Device Outdoors

    The lightning protector must meet the necessary requirements of IEC/UL/CSA 62368-1. The clamping voltage must also be less than 60 V and the protector must not activate when the voltage is less than 56 V. For more information, contact Siemens Customer Support. RUGGEDCOM RP100 Installation Manual, 01/2021, C79000-G8976-1011-05...
  • Page 18: Grounding The Device

    Installing the Device 2.5 Grounding the Device IMPORTANT Install the lightning protector and RP100 as close as possible. CPE/PD Shielded Cable Ground Connection Lightning Protector RP100 Drain Wire (Shielded) Figure 2.3 Typical Outdoor Installation Grounding the Device The RP100 chassis ground terminal uses a #6-32 screw. It is recommended to terminate the ground connection with a #6 ring lug and torque it to 8.3 N·m (6 lbf·in).
  • Page 19: Connecting Power

    Installing the Device 2.6 Connecting Power Connecting Power The RP100 supports a single high AC, high DC or low DC power supply. Note • For 100-240 VAC rated equipment, an appropriately rated AC circuit breaker must be installed. • For 125-250 VDC rated equipment, an appropriately rated DC circuit breaker must be installed.
  • Page 20: 2.6.2 Connecting Dc Power

    Installing the Device 2.6.2 Connecting DC Power Connect the positive wire from the power source to the positive/live (+/L) terminal on the terminal block. Positive/Live (+/L) Terminal Negative/Neutral (-/N) Terminal Surge Ground Terminal Braided Ground Cable Figure 2.5 Terminal Block Wiring Connect the negative wire from the power source to the negative/neutral (-/N) terminal on the terminal block.
  • Page 21 Installing the Device 2.6.2 Connecting DC Power Connect the positive wire from the power source to the positive/live (+/L) terminal on the terminal block. Positive/Live (+/L) Terminal Negative/Neutral (-/N) Terminal Surge Ground Terminal Braided Ground Cable Figure 2.6 Terminal Block Wiring Connect the negative wire from the power source to the negative/neutral (-/N) terminal on the terminal block.
  • Page 22: Device Management

    Device Management This section describes how to connect to and manage the device. Connecting a RUGGEDCOM WIN Subscriber Station The RUGGEDCOM RP100 is designed to be a Power-over-Ethernet (POE) injector for RUGGEDCOM WIN5000 series subscriber stations. IMPORTANT If the RUGGEDCOM RP100 is to be installed outdoors, make sure the connection between both devices is bridged by a suitably rated lightening protector.
  • Page 23 Device Management 3.1 Connecting a RUGGEDCOM WIN Subscriber Station RUGGEDCOM RP100 Installation Manual, 01/2021, C79000-G8976-1011-05...
  • Page 24: Communication Ports

    Communication Ports The RP100 supports a copper 10/100Base-TX Ethernet port and a 10/100Base-TX PoE (Power over Ethernet) Ethernet port, both with RJ45 connectors. The RJ45 connectors are directly connected to the chassis ground on the device and can accept CAT-5 shielded twisted-pair (STP) cables. The PoE port injects power on pins 4, 5, 7 and 8.
  • Page 25 Communication Ports Signal Non-PoE Terminated Case Shield (Chassis Ground) RUGGEDCOM RP100 Installation Manual, 01/2021, C79000-G8976-1011-05...
  • Page 26: Technical Specifications

    Technical Specifications This section provides important technical specifications related to the device. Power Supply Specifications Rated Input Rated Output Power Voltage Current 12 VDC 3.5 A 52 VDC (PoE), 25 W, @ 85 °C (185 °F) 24 VDC 52 VDC (PoE), 32 W, @ 85 °C (185 °F) 48 VDC 100-240 V~, 50-60 Hz...
  • Page 27: Dimension Drawings

    Technical Specifications 5.4 Dimension Drawings Dimension Drawings Note All dimensions are in millimeters, unless otherwise stated. 77.2 56.6 11.4 95.0 Figure 5.1 Overall Dimensions RUGGEDCOM RP100 Installation Manual, 01/2021, C79000-G8976-1011-05...
  • Page 28: Certification

    Products with Respect to the Restriction of Hazardous Substances The device is marked with a CE marking and can be used throughout the European community. A copy of the CE Declaration of Conformity is available from Siemens AG. For contact information, refer to "Contacting Siemens (Page vi)".
  • Page 29: 6.1.2 Tüv Süd

    6.1.4 ISED This device is declared by Siemens AG to meet the requirements of the following ISED (Innovation Science and Economic Development Canada) standard: • CAN ICES-3 (A)/NMB-3 (A) 6.1.5...
  • Page 30 A copy of the Declaration of Conformity is available via Siemens Industry Online Support at https://support.industry.siemens.com/cs/ww/en/view/89855782. 6.1.7 RoHS This device is declared by Siemens AG to meet the requirements of the following RoHS (Restriction of Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic equipment: •...
  • Page 31 Certification 6.2 EMC and Environmental Type Tests Test Description Test Levels Severity Levels Enclosure Air ± 15 kV Radiated RFI Enclosure 20 V/m 61000-4-3 Ports Burst (Fast Transient) Signal Ports ± 4 kV @ 2.5 kHz 61000-4-4 DC Power ± 4 kV Ports AC Power ±...
  • Page 32 Certification 6.2 EMC and Environmental Type Tests Test Description Test Levels Severity Levels AC Power 5 kV   Ports Shielded cable used. IEEE 1613 EMC Immunity Type Tests Note The RUGGEDCOM RP100 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for copper ports. Description Test Levels Enclosure Contact...
  • Page 33 Certification 6.2 EMC and Environmental Type Tests RUGGEDCOM RP100 Installation Manual, 01/2021, C79000-G8976-1011-05...
  • Page 34 Further Information Siemens RUGGEDCOM https://www.siemens.com/ruggedcom Industry Online Support (service and support) https://support.industry.siemens.com Industry Mall https://mall.industry.siemens.com Siemens AG Digital Industry Process Automation Postfach 48 48 90026 NÜRNBERG GERMANY...

This manual is also suitable for:

Ruggedcom rp100

Table of Contents