Com1 Communication Address; Com1 Transmission Speed; Com1 Transmission Fault Treatment; Com1 Communication Protocol - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

09 Communication Parameters

COM1 Communication Address

Settings 1~254
If the AC motor drive is controlled by RS-485 serial communication, the communication address
for this drive must be set via this parameter. And the communication address for each AC motor
drive must be different and unique.

COM1 Transmission Speed

Settings 4.8~115.2 Kbps
This parameter is used to set the transmission speed between the RS485 master (PLC, PC, etc.)
and AC motor drive.

COM1 Transmission Fault Treatment

Settings
This parameter is set to how to react if transmission errors occur.
COM1 Time-out Detection
Settings 0.0~100.0 sec
It is used to set the transmission time between communication and keypad.

COM1 Communication Protocol

Settings 1: 7, N, 2 for ASCII
When us ing communication devi ces,
connects AC dr ive with P C by us ing
Delt a I FD6530 or I FD6500.
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
0.0: Disable
2: 7, E, 1 for ASCII
3: 7, O, 1 for ASCII
4: 7, E, 2 for ASCII
5: 7, O, 2 for ASCII
6: 8, N, 1 for ASCII
7: 8, N, 2 for ASCII
8: 8, E, 1 for ASCII
Chapter 12 Description of Parameter Settings|C2000 Series
The parameter can be set during the operation.
8
1
M odbus RS- 485
Pin 1~2,7, 8: Reserv ed
Pin 3, 6: GND
Pin 4: SG-
Pin 5: SG+
RS-485
12-133
Factory Setting: 1
Factory Setting: 9.6
Factory Setting: 3
Factory Setting: 0.0
Factory Setting: 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents