Heat Sink Over-Heat (Oh) Warning - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

1: Standard motor
2: Disable
It is used to prevent self-cooled motor overheats under low speed. User can use electronic thermal
relay to limit driver's output power.
Electronic Thermal Characteristic for Motor 1
Electronic Thermal Characteristic for Motor 2
Settings 30.0~600.0 sec
The parameter is set by the 150% of motor rated current and the setting of Pr.06-14 and Pr.06-28 to
prevent the motor damaged from overheating. When it reaches the setting, it will display
"EoL1/EoL2" and the motor will be in free running.

Heat Sink Over-heat (OH) Warning

0.0~110.0℃
Settings
Pr.06-15 sets the heatsink temperature level of the drive. The drive will output an overheating
warning when the temperature exceeds the setting of Pr.06-15. If the setting of Pr.06-15 is higher
than the default setting of the drive, the drive will use the default setting level for warning output.
Capacitor (CAP) overheating level is set by the drive's default setting, it can not be adjusted.
Over-heating Level (℃)
Model
IGBT OH1
VFD007C23A/E
VFD015C23A/E
VFD022C23A/E
VFD037C23A/E
VFD055C23A/E
VFD075C23A/E
VFD110C23A/E
VFD150C23A/E
VFD185C23A/E
VFD220C23A/E
VFD300C23A/E
VFD370C23A/E
Chapter 12 Description of Parameter Settings|C2000 Series
Operation
time(min)
5
4
3
2
1
0 20 40 60 80100120140160180200
CAP OH 2
100
90
100
90
100
90
100
95
100
75
100
75
100
75
95
70
95
70
95
70
95
60
95
60
12-98
Factory Setting: 60.0
60Hz or more
50Hz
10Hz
5Hz
Load
factor (%)
Factory Setting: 85.0
Over-heating Level (℃)
Model
IGBT OH1
VFD055C43A/E
VFD075C43A/E
VFD110C43A/E
VFD150C43A/E
VFD185C43A/E
VFD220C43A/E
VFD300C43A/E
VFD370C43A/E
VFD450C43A/E
VFD550C43A/E
VFD750C43A/E
VFD900C43A/E
CAP OH 2
100
95
95
75
95
75
95
75
95
80
95
80
100
80
95
60
95
60
100
60
100
60
100
60

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents