Delta C2000 series User Manual page 389

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Chapter 14 Fault Codes and Descriptions |C2000 Series
Fault Name
Fault
PGr1
PG Ref error
Fault
PGr2
PG Ref loss
Fault
ACE
ACI loss
Fault
EF
External fault
Fault
EF1
Emergency stop
Fault
bb
Base block
Fault
Pcod
Password error
Fault
CE1
PC err command
Fault
CE2
PC err address
Fault
CE3
PC err data
Fault Descriptions
Pulse input error
Pulse input loss
ACI loss
External Fault
Emergency stop
External Base Block
Password is locked.
Illegal function code
Illegal data address (00H
to 254H)
Illegal data value
Corrective Actions
1.
Check the pulse wiring
2.
Return to the factory
1. Check the pulse wiring
2. Return to the factory
1. Check the ACI wiring
2. Check if the ACI signal is less than 4mA
1. Input EF (N.O.) on external terminal is closed to
GND. Output U, V, W will be turned off.
2. Give RESET command after fault has been
cleared.
1. When the multi-function input terminals MI1 to
MI6 are set to emergency stop, the AC motor
drive stops output U, V, W and the motor coasts
to stop.
2. Press RESET after fault has been cleared.
1. When the external input terminal (B.B) is active,
the AC motor drive output will be turned off.
2. Deactivate the external input terminal (B.B) to
operate the AC motor drive again.
Keypad will be locked. Turn the power ON after
power OFF to re-enter the correct password. See
Pr.00-07 and 00-08.
Check if the function code is correct (function code
must be 03, 06, 10, 63)
Check if the communication address is correct
Check if the data value exceeds max./min. value
14-6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents