Delta VFD-B Series User Manual

Delta VFD-B Series User Manual

High performance/user-friendly powerful ac motor drives
Hide thumbs Also See for VFD-B Series:
Table of Contents

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Delta VFD-B Series

  • Page 2 5011025709 200310-27 BE11...
  • Page 4 WARNING Always read this manual thoroughly before using VFD-B series AC Motor Drives. DANGER! AC input power must be disconnected before any maintenance. Do not connect or disconnect wires and connectors while power is applied to the circuit.
  • Page 6 4.1 Description of the Digital Keypad VFD-PU01 ........4 - 2 4.2 Operation steps of the Digital Keypad VFD-PU01......4 - 4 CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS Group 0: User Parameters ............... 5 - 1 Group 1: Basic Parameters ..............5 - 5 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 7 APPENDIX A SPECIFICATIONS ............... A - 1 APPENDIX B ACCESSORIES B.1 Non-fused Circuit Breaker and Fuse Specification Chart....B - 1 B.2 Braking Resistors & Braking Units ............. B - 3 B.3 AMD-EMI Filter Cross Reference............B - 7 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 8 B.4 PG Cards ................... B-16 B.5 Remote Controller RC-01..............B-22 B.6 Remote Panel Adapter ............... B-23 B.7 Zero Phase Reactor ................B-24 APPENDIX C DIMENSIONS............... C - 1 APPENDIX D EC DECELERATION OF CONFORMITY......D - 1 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 9 007: 1 HP(0.7kW) 150: 20HP(15kW) Series Name 022: 3 HP(2.2kW) 220: 30 HP(22kW) 037: 5 HP(3.7kW) 300: 40HP(30kW) 055: 7.5HP(5.5kW) 370: 50 HP(37kW) 075: 10 HP(7.5kW) 450: 60HP(45kW) 110: 15 HP(11kW) 550: 75HP(55kW) 750: 100HP(75kW) DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 10 007B23A0 Production number Production week Production year 2003 Production factory (Taoyuan) 230V 3-phase 1HP(0.75kW) Model If there is any nameplate information not corresponding to your purchase order or any problem, please contact your distributor. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 11 Relative Humidity: Less than 90%, no condensation allowed Atmosphere pressure: 86 to 106 kPa Vibration: Maximum 9.80 m/s (1G) at less than 20Hz, Maximum 5.88 (0.6G) at 20Hz to 50Hz Pollution Degree 2: good for a factory type environment. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 12 Mount the AC drive vertically and do not restrict the air flow to the heat sink fins. The AC drive generates heat. Allow sufficient space around the unit for heat dissipation. 120mm Air Flow PROG DATA 120mm DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 13 Wait five minutes for DC bus capacitors discharge. Any electrical or mechanical modification to this equipment without prior written consent of Delta Electronics, Inc. will void all warranties and may result in a safety hazard in addition to voiding the UL listing.
  • Page 14 Modem or telephone line to the RS-485 communication port, permanent damage may result. Terminals 1 & 2 are the power sources only for the optional copy keypad and should not be used while using RS-485 communication. Figure 1 for models of VFD-B Series VFD007B21A/23A/43A, VFD015B21A/21B/23A/23B/43A VFD022B23B/43B...
  • Page 15 VFD-B Series Figure 2 for models of VFD-B Series 3-15 HP VFD022B21A, VFD037B23A/43A, VFD055B23A/43A, VFD075B23A/43A, VFD110B23A/43A * Three phase input power may apply to single phase drives. * For the single phase application, the AC input line can be connected to any two of the three input terminals R,S,T...
  • Page 16 VFD-B Series Figure 3 for models of VFD-B Series 20 HP and above VFD150B23A/43A, VFD185B23A/43A, VFD220B23A/43A, VFD300B23A/43A, VFD370B23A/43A, VFD450B43A, VFD550B43A, VFD750B43A DC chock (optional) VFDB Jumper Fuse/NFB(None Fuse Breaker) -(minus sign) Motor R(L1) R(L1) U(T1) S(L2) S(L2) V(T2) T(L3) T(L3)
  • Page 17 VFD-B Series Figure 4 Wiring for SINK mode and SOURCE mode Sink Source DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 18 Appendix B for specific Braking (Optional) Resistors. Output AC Motor surge voltage amplitudes Line depending on the motor cable Reactor length. For long motor cable (Optional) application, it is necessary installed on the inverter output side. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 19 Digital Frequency Meter Factory setting 1:1 (Maximum 48VDC, 50mA) (Open Collector Output) DC Voltage Source +24V (+24V, 20mA), used for source mode. Used as common for digital inputs Digital Signal Common and used for sink mode. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 20 Analog voltage Input 4 to 20mA Analog current Input Auxiliary analog voltage input -10 to +10V Analog output meter 0 to 10V, 2mA Analog control signal (common) * Control signal wiring size: 18 AWG (0.75 mm DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 21 / T3 Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal Torque: 18 kgf-cm (15.6 in-lbf) Wire Gauge: 10-18 AWG stranded wire, 12-18 AWG solid wire Wire Type: Copper only, 75° C DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 22 Wire Gauge : 18~10AWG R/L1 S/L2 T/L3 Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal ]Torque: 18 kgf-cm (15.6 in-lbf) Wire Gauge: 10-18 AWG Wire Type: Stranded copper only, 75° C 3-10 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 23 Wire Type: Stranded Copper only, 75° C NOTE: If wiring of the terminal utilizes the wire with a 6AWG-diameter, it is thus necessary to use the Recognized Ring Terminal to conduct a proper wiring. 3-11 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 24 Wire Type: Stranded Copper only, 75° C NOTE: If wiring of the terminal utilizes the wire with a 1AWG-diameter, it is thus necessary to use the Recognized Ring Terminal to conduct a proper wiring. 3-12 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 25 Screw Torque: POWER MOTOR 200kgf-cm (173in-lbf) Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal Torque: 200kgf-cm (173 in-lbf) Wire Gauge: 2/0 - 3/0 AWG Wire Type: Stranded copper only, 75°C 3-13 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 26 R/L1 S/L2 T/L3 U/T1 V/T2 2/T3 POWER MOTOR Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal Torque: 58.7kgf-cm (50.9 in-lbf) max. Wire Gauge: 2-4AWG Wire Type: Stranded copper only, 75°C 3-14 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 27 Screw Torque: POWER MOTOR 200kgf-cm ( 173in- lbf) Control Terminal Torque: 4Kgf-cm (3 in-lbf) Wire: 12-24 AWG Power Terminal Torque: 200 kgf-cm (173 in-lbf) Wire Gauge: 2/0-3/0 AWG Wire Type: Stranded copper only, 75°C 3-15 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 28 U/T1, V/T2, and W/T3, respectively, the motor will rotate counterclockwise (as viewed from the shaft ends of the motor) when a forward operation command is received. To reverse the direction of motor rotation, switch over any of the two motor leads. 3-16 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 29 3. When the standard motor operates at low speed, the output load must be decreased. 4. If 100% output torque is desired at low speed, it may be necessary to use a special “inverter-duty” rated motor. 3-17 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 31 Description of the Keypad Description of Display Keypad Operation Modes & Programming Steps VFD-PU01 Dimensions: mm (inch) 19.0 [0.75] 44.0 [1.73] 73.0 [2.87] M4* 0.7(2X) MODE PROG DATA STOP DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 32 RUN key Master Frequency. Display Message Descriptions Display the AC drive Master Frequency. Display the actual operation frequency present at terminals U/T1, V/T2, and W/T3. User defined unit, where (U = F x Pr.00-05) DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 33 Display “End” for approximately 1 second if input has been accepted. After a parameter value has been set, the new value is automatically stored in memory. To modify an entry, use the keys. Display “Err”, if the input is invalid. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 34 Input data error move to previous display MODE NOTE : In the parameter setting mode, you can press to return the selecting mode. MODE To shift data START To modify data START Setting direction DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 35 (Pr.06-08 ~ Pr06-11). If this parameter is set to 08, the operation function of VFD-PU01 keypad is disabled. At this time, you should set Pr.00-02 to 00 to disable parameter lock function. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 36 The coefficient K determines the multiplying factor for the user-defined unit. The display value is calculated as follows: U (user-defined unit) = Frequency Command x K (Pr.00-05) H (actual output) = (actual output frequency) x K (Pr.00-05) DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 37 0 in the parameter as a password. To change the one of the parameter settings of this AC drive, one must enter the correct password in Pr.00-07 to activate this function. Be sure to keep the password in mind for later use. Display states: DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 38 00 - 09 Control methods Factory Setting: 00 Settings V/F control V/F + PG Control Vector Control Vector + PG Control This parameter determines the control methods of the AC drive. 00 - 10 Reserved DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 39 This parameter sets the Mid-Point Voltage of any V/F curve. With this setting, the V/F ratio between Minimum Frequency and Mid-Point Frequency can be determined. This parameter must be equal to or greater than Minimum Output Voltage (Pr.01-06) and DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 40 01-02 Maximum Output Voltage 01-04 Mid-point Voltage Output Frequency 01-06 setting limit Minimum Output Voltage 01-01 01-00 01-05 01-03 Minimum Mid-point Maximum Maximum Voltage Output Freq. Output Frequency Freq. Frequency (Base Frequency) V/F Curve DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 41 Maximum Output Frequency (Pr.01-00) down to 0 Hz. The rate is linear unless S-Curve is “Enabled.” The Acceleration/Deceleration Time 1, 2, 3, 4 is switched according to the Multi-Function Input Terminals Setting . See Pr.04-04 to Pr.04-09 for more details. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 42 Jog Accel/Decel time (Pr.01-13, Pr01-22). During operation, the AC drive cannot perform Jog command. And during Jog operation, other operation commands cannot be accepted, except command of FORWARD, REVERSE and STOP keys on the digital keypad. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 43 NOTE: From the diagram shown below, the original setting Accel/Decel Time will be for reference when the function of the S-curve is enabled. The actual Accel/Decel Time will be determined based on the S-curve selected (01 to 07). DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 44 Unit: 1 sec Unit: 0.1 sec Unit: 0.01 sec This parameter can be used to set the unit of Accel/Decel Time and the setting range of Accel/Decel Time is also changed at the same time. 5-10 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 45 Master Frequency determined by RS-485 serial communication. (RJ-11). It won’t memorize the frequency. Combined usage of the master and auxiliary frequency command Pr. 02-10, 02-11,02-12 These parameters set the Frequency Command Source of the AC drive. 5-11 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 46 2. Coast: the AC drive stops output instantly upon command, and the motor free runs until it comes to a complete stop. 3. The motor stop method is usually determined by the characteristics of the motor load and the frequency of stop 5-12 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 47 Significant Significant From the table, we see that the PWM carrier frequency has a significant influence on the electromagnetic noise, heat dissipation of the AC drive, and the acoustic noise to the motor. 5-13 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 48 FWD/ REV 2-wire RUN / STOP REV:("OPEN": F FWD/STOP ("CLOSE": REV) VFD-B STOP FWD:("CLOSE":RUN) EF: ("OPEN":STOP) REV:("OPEN": F 3-wire RUN/FWD ("CLOSE": REV) VFD-B 02- 06 Line Start Lockout Factory Setting: 00 Settings Disable Enable 5-14 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 49 02 - 10 Source of the Master Frequency Command (FCHA) Factory Setting: 00 Settings Digital keypad 0 to +10V from AVI 4 to 20mA from ACI -10 to +10Vdc from AUI RS-485 communication interface 5-15 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 50 06. If they are enabled, the frequency command will be determined by these parameters. Keyboard Frequency Command Factory Setting: 60.00 02 - 15 Settings 0.00 ~ 400.00Hz Unit: 0.01 This parameter can be used to set frequency command or read keypad frequency command. 5-16 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 51 The Output will be activated for 0.5 sec when PLC Program Step Completed each multi-step speed is attained. The output will be activated for 0.5 sec when PLC Program Completed the PLC program cycle has completed 5-17 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 52 The output will be activated once the DC Bus voltage is too low. (Refer to Pr.06-16, User-defined low-voltage Detection Pr.06-17) Desired Frequency Attained 1 Factory Setting: 0.00 03 - 04 Settings 0.00 to 400.00 Hz Unit: 0.01Hz 5-18 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 53 This parameter determines the meaning of the 0~+10VDC output from AFM and ACM. 03 - 06 Analog Output Gain Factory Setting: 100 Settings 01 to 200% Unit: 1% This parameter sets the voltage range of the analog output signal. 5-19 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 54 When the counter value is counted up from “1” to the set value of this parameter, the corresponding multi-function output terminal will be activated, when set to 15 (Preliminary Count Value Setting). The corresponding multi-function output terminal will be deactivated upon completion of Terminal Count Value Attained. 5-20 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 55 Always fan on Power off 1 minute later, fan off Run and fan on, stop and fan off Preliminary temperature attained, Fan start to run This parameter determines the operation mode of cooling fan. 5-21 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 56 Negative bias, REV motion disabled Factory Setting: 0.00 04 - 15 AUI Analog Input Bias Settings 0.00 to 100.00% Unit: 0.01% Factory Setting: 00 04 - 16 AUI Bias Polarity Settings Positive Bias Negative Bias 5-22 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 57 60Hz Factory Settings Pr.01-00=60Hz--Max. output Freq. Pr.04-11=16.7%-- bias adjustment Pr.04-12=0 -- bias polarity Pr.04-13=100% -- pot. freq. gain 10Hz Pr.04-14=0 -- REV motion disable in negative bias Bias Adjustment 0Hz 0V 20mA 12mA 5-23 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 58 Max. Output Freq. Pr.01-00 Factory Settings 60Hz Pr.01-00=60Hz--Max. output Freq. 54Hz Pr.04-11=10.0% -- bias adjustment Pr.04-12=1 -- bias polarity Pr.04-13=100% -- pot. freq. gain Pr.04-14=0 -- Rev. motion disable in negative bias Negative bias 6Hz 5-24 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 59 20 mA or 10V. With anti-slope enable, the large signal will slow or stop the AC drive. The limit in this application is can’t change the direction of run. For AC drive, it just can run in reverse direction. 5-25 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 60 Note: the External Reset has the same function as 05 External Reset (NO)** the Reset key on the Digital keypad. After fault such as O.H., O.C. and O.V. are clear, this input can be used to reset the drive. 5-26 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 61 Parameter value 19 to 20 program Multi-Function Input Terminal to the AC drive to receive the signals of malfunction and emergency stop. Please press “RESET” after fault has been cleared. Emergency Stop (NC)*** 5-27 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 62 It can be cancel by “STOP” command. Proximity sensor input for This function should be used with Pr.04-23 ~ simple Index function Pr.04-25. 5-28 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 63 Accel/Decel time 1 & 2 Multi-function Input Terminals Pr.04-04 to Pr.04-09(MI1 to MI6 7) Accel/Decel time 3 & 4 Multi-function Input Terminals Pr.04-04 to Pr.04-09(MI1 to MI6 8) Accel/Decel Time and Multi-function Input Terminals 5-29 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 64 0.00 to 10.00 Sec Unit: 0.01 Factory Setting: 0.05 04 - 21 AUI Analog Input Delay Settings 0.00 to 10.00 Sec Unit: 0.01 04 - 22 Analog Input Frequency Resolution Factory Setting: 01 Settings 0.01Hz 0.1Hz 5-30 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 65 When the stop command is accepted, the AC drive will not decelerate until the sensor is trigged, then the AC drive begin to decelerate and stop according to the Pr.04-24 and Pr.04-25. 5-31 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 66 Continuously execute program cycles step by step This parameter selects the mode of PLC operation for the AC drive. The AC drive will change speeds and directions according to the user’s desired programming. 5-32 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 67 The diagram above shows the PLC program stepping through each speed. Set Pr.05-15 to 2 continuously executes the program. To stop the PLC program, one must either pause the program or turn it off. (Refer to Pr.04-04 to 04-09 values 14 and 15). 5-33 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 68 The equivalent 15-bit number is used to program the forward/reverse motion for each of the 15 speed steps. The binary notation for the 15-bit number must be translated into decimal notation and then entered. 5-34 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 69 Setting 05-16 =19570 NOTE: 2 =16384 2 =8192 2 =4096 2 =2048 2 =1024 2 =512 2 =256 2 =128 2 =64 2 =32 2 =16 2 =8 2 =4 2 =2 2 =1 5-35 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 70 Factory Setting: 0.00 Settings 0.00〜400.00 Hz Frequency of ∆ top point F = master frequency F + Pr.05-33 + Pr.05-34. Frequency of ∆ down point F = master frequency F – Pr.05-33 – Pr.05-34. down 5-36 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 71 VFD-B Series Double Pr. 05-34 Pr.05-33 Pr.01-09 Master Pr.01-11 Frequency Pr.01-10 Pr.01-12 Fdown 5-37 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 72 Pr.06-01 due to rapid acceleration or excessive load on the motor. When this function is enabled, the AC drive will stop accelerating and keep the output frequency until the current drops below the maximum value. 5-38 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 73 Pr.06-02, the drive will then accelerate to catch up with the frequency specified. Over-Current Detection Output Current Level 06-02 Over-Current Stall Prevention during Operation, output frequency decrease Output Frequency 5-39 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 74 30 to d 600 Sec Unit: 1 Sec The parameter determines the time required activating the I t electronic thermal protection function. The graph below shows I t curves for 150% output power for 1 minute. 5-40 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 75 Current exceeds 2 times rated current during decel.(ocd) Current exceeds 2 times rated current during steady state operation (ocn) Ground fault (GFF) Low voltage (Lv) CPU READ failure (CF1) CPU WRITE failure (CF2) 5-41 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 76 If output current is lower than Pr.06-12 and exceed the time that Pr.06-13 sets during running, AC drive will warn as Pr.06-14 sets. If Pr.06-14 is set to 03, AC drive will restart after the delay time set by Pr.06-15 is up. 5-42 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 77 When the voltage of DC BUS is lower than Pr.06-16 and the time exceeds the setting of Pr.06-17, AC drive will output a signal by the setting 28 of Pr.03-00 ~ Pr.03-03. 06 - 18 Reserved 5-43 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 78 This parameter sets the number of motor poles (must be an even number). Factory Setting: 00 07 - 05 Motor Parameters Auto Tuning Settings Disable Unit: 1 Auto Tuning R1 Auto Tuning R1 + No-load Test 5-44 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 79 Refer to the rated rpm on the nameplate of the motor and use the following equation to determine the rated slip. Rated Slip = F (Pr.01-01 base frequency) – (rated rpm x motor pole/120) 5-45 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 80 00 ~65535 Unit: 01 Pr.07-14 and Pr.07-15 are used to record the motor operation time. They can be cleared by setting to 00 and won’t record if the time is less than 60 seconds. 5-46 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 81 NOTE: 1. DC Braking during Start-up is used for loads that may move before the AC drive starts, such as fans and pumps. Under such circumstances, DC Braking can be executed to hold the load in position before applying a forward motion. 5-47 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 82 30 to 200% Unit: 1% This parameter limit the current output when the Drive operates in speed search mode. When executing speed search, V/F curve will base on the setting of Group 01. 5-48 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 83 When enabled, the AC drive will restart with speed search, which starts at the Frequency before fault. Factory Setting: 00 08 - 15 Automatic energy-saving Settings Energy-saving operation disabled Energy-saving operation enabled 5-49 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 84 Software Setting of the Braking Level 08 - 17 Unit: 1 (the Action Level of the Braking Resistor) Settings 230V series: 370 to 430V Factory Setting: 380 460V series: 740 to 860V Factory Setting: 760 5-50 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 85 08-06 Speed search level Speed Search Output current Time FWD R un B.B. Fig 2: B.B. Speed Search with Last Output Frequency Downward Timing Chart (Speed Search Current doesn't Attain Speed Search Level) 5-51 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 86 Factory Setting: 00 08 - 20 Speed Search Frequency during Start-up Settings Setting Frequency Maximum Operation Frequency (01-00) This parameter determines the start frequency of speed search frequency. 5-52 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 87 10. Factory Setting: 00 08 - 22 Compensation Coefficient for Motor Instability Settings 00~1000 Unit: 1 This parameter can improve the motor instability situation. 5-53 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 88 Modbus ASCII mode, protocol <7,N,2> Modbus ASCII mode, protocol <7,E,1> Modbus ASCII mode, protocol <7,O,1> Modbus RTU mode, protocol <8,N,2> Modbus RTU mode, protocol <8,E,1> Modbus RTU mode, protocol <8,O,1> 1. Computer Control 5-54 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 89 ‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’ ASCII code RTU mode: Each 8-bit data is the combination of two 4-bit hexadecimal characters. For example, 64 Hex. 2. Data Format 10-bit character frame (For ASCII): 5-55 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 90 50 ASCII codes LRC CHK 1 LRC check sum: LRC CHK 0 8-bit check sum consists of 2 ASCII codes END 1 End characters: END1= CR (0DH), END0= LF(0AH) END 0 RTU mode: 5-56 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 91 ‘4’ address ‘0’ ‘1’ Content of ‘2’ ‘7’ register ‘0’ ‘7’ 2102H Number of data ‘0’ ‘0’ (count by word) ‘0’ Content of ‘0’ ‘2’ register 2103H ‘0’ LRC CHK 1 ‘D’ ‘0’ 5-57 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 92 Data content Data content ‘7’ ‘7’ ‘0’ ‘0’ LRC CHK 1 ‘7’ LRC CHK 1 ‘7’ LRC CHK 0 ‘1’ LRC CHK 0 ‘1’ END 1 END 1 END 0 END 0 RTU mode: 5-58 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 93 Response message: CMD 1 Data address Data address 17H’ Data content Data content CRC CHK Low CRC CHK Low CRC CHK High CRC CHK High (4) 10H: multi write, write multi data to registers. 5-59 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 94 Number of data 00H’ Number of data (count by word) (count by word) Number of data CRC Check Low (count by byte) CRC Check High The first data content The second data 0FH 5-60 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 95 Step 1: Load a 16-bit register (called CRC register) with FFFFH. Step 2: Exclusive OR the first 8-bit byte of the command message with the low order byte of the 16-bit CRC register, putting the result in the CRC register. 5-61 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 96 ^= *data++; for(j=0;j<8;j++){ if(reg_crc & 0x01){ /* LSB(b0)=1 */ reg_crc=(reg_crc>>1) ^ 0xA001; }else{ reg_crc=reg_crc >>1; return reg_crc; 3.5 Address list: The contents of available addresses are shown as below: 5-62 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 97 10: Current exceeds 2 times rated current during accel (ocA) 11: Current exceeds 2 times rated current during decel (ocd) Status monitor 2100H 12: Current exceeds 2 times rated current during steady state Read only operation (ocn) 13: Ground Fault (GFF) 5-63 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 98 Output voltage E (XXX.X) 2107H Step number of Multi-Step Speed Operation 2108H Step number of PLC operation 2109H Content of external TRIGGER 210AH Power factor angle 210BH Estimated torque ratio 210CH Motor speed (Hz) 5-64 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 99 CMD 1 ‘8’ CRC CHK Low CMD 0 ‘6’ CRC CHK High ‘0’ Error code ‘2’ LRC CHK 1 ‘7’ LRC CHK 0 ‘7’ END 1 END 0 The explanation of error codes: 5-65 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 100 /* read 2 data from address 2102H of AC drive with address 1 */ unsigned char tdat[60]={':','0','1','0','3','2','1','0',’2', '0','0','0','2','D','7','\r','\n'}; void main(){ int i; outportb(PORT+MCR,0x08); /* interrupt enable */ outportb(PORT+IER,0x01); /* interrupt as data in */ outportb(PORT+LCR,(inportb(PORT+LCR) | 0x80)); /* the BRDL/BRDH can be access as LCR.b7==1 */ 5-66 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 101 RS485 BUS PC or PLC command Response Message of AC Drive Handling time Response Delay Time of AC drive * This parameter is only for version 4.01 and higher. 5-67 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 102 This parameter specifies integral control (continual sum of the deviation) and associated gain (I). When the integral gain is set to 1 and the deviation is fixed, the output is equal to the input (deviation) once the integral time setting is attained. 5-68 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 103 This parameter defines the percentage of output frequency limit during the PID control. The formula is Output Frequency Limit = Maximum Output Frequency (Pr.01-00) X Pr.10-07 %. This parameter will limit the Maximum Output Frequency. 5-69 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 104 PG control. 10 - 11 PG Input Factory Setting: 00 Settings Disable PG Single phase Forward / Counterclockwise rotation Reverse / Clockwise rotation The relationship between the motor rotation and PG input as below: 5-70 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 105 Frequency Command Output Frequency Output Frequency Limit 10-12 10-14 Speed Detection 10-13 Speed Control Diagram Sample time for refreshing the content of 210DH and Factory Setting: 0.10 10 - 15 210EH Settings 0.01~1.00 seconds 5-71 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 106 Freq. filter Setpoint limit Limit Command 10-02 10-03 10-06 10-05 10-07 10-04 Input Freq. Gain feedback 10-00 10-01 Speed Control Diagram Frequency Command Output Frequency Output Frequency Limit 10-12 10-14 Speed Detection 10-13 5-72 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 107 Time Delay before Starting the Auxiliary Motor Settings 0.0 to 3600.0 sec Unit: 0.1 Factory Setting: 0.0 11 - 04 Time Delay before Stopping the Auxiliary Motor Settings 0.0 to 3600.0 sec Unit: 0.1 5-73 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 108 Factory Setting: 0.0 Sleep/Wake Up Detection Time 11 - 05 Settings 0.0 to 6550.0 sec Unit: 0.1 Factory Setting: 0.00 11 - 06 Sleep Frequency Settings 0.00 to Fmax Unit: 0.01Hz 5-74 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 109 When actual output frequency H < Pr.11-06 and time exceeds the setting of Pr.11-05, AC drive will be in sleep mode. When actual frequency command > Pr.11-07 and time exceeds the setting of Pr.11-05, Ac drive will restart. 5-75 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 111 Clean off any dust and dirt with a vacuum cleaner. Place special emphasis on cleaning the ventilation ports and PCBs. Always keep these areas clean, as accumulation of dust and dirt can cause unforeseen failures. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 113 3. Bus over-voltage may also be caused has exceeded its by motor regeneration. Either increase maximum allowable the decel time or add an optional value. braking resistor. 4. Check whether the required braking power is within the specified limits. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 114 (Pr.6-03 to Pr.6-05) to an appropriate setting (Pr.06-03 to Pr.06-05). 1. Check the connection between the AC drive and computer for loose wires. Communication Error 2. Check if the communication protocol is properly set. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 115 1. When external terminal EF-GND is closed, the output will be turned off. The external terminal (Under N.O. E.F.) EF-GND goes from OFF to ON. 2. Press RESET after fault has been cleared. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 116 AC drive 2. Check for possible poor insulation at the power module may be output line. damaged. The short circuit protection is provided for AC drive protection, not user protection. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 117 2. Retry again 1. Check counter trigger signal EF when preliminary count value attained 2. Check Pr.03-09, Pr.03-11setting 1. Check Load current Low Current 2. Check Pr.06-12 to Pr.06-15 setting Phase Loss Check Power Source Input DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 119 08: Display the estimative value of the ration of torque (t) 09: Display PG numbers/10ms (G) 10: Display analog feedback signal value (b) 11: Display AVI (U1.) (%) 12: Display ACI (U2.) (%) 13: Display AUI (U3.) (%) DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 120 #.## 00-07 Password Decode 1 to 65535 00-08 Password Input 0 to 65535 00: V/F Control 01: V/F + PG Control 00-09 Control Methods 02: Vector Control 03: Vector + PG Control 00-10 Reserved DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 121 01-21 Decel Time 4 0.01 to 3600.0 sec 10.0 01-22 Jog Deceleration Time 0.01 to 3600.0 sec 00: Unit: 1 sec 01-23 Unit for Accel/Decel Time 01: Unit: 0.1 sec 02: Unit: 0.01 sec DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 122 02-04 Motor Direction Control 01: Disable Reverse operation 02: Disabled Forward operation 00: FWD/STOP, REV/STOP 2-wire/3-wire Operation 02-05 01: FWD/REV, RUN/STOP Control Modes 02: 3-wire Operation 00: Disable 02-06 Line Start Lockout 01: Enable DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 123 Pr. 02-10, 02-11,02-12 02-14 00: Controlled by the digital keypad Source of Second 01: Controlled by the external terminals, Operation Command keypad STOP enabled. 02: Controlled by the external terminals, keypad STOP disabled. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 124 VFD-B Series Factory Parameters Explanation Settings Setting 03: Controlled by the RS-485 communication interface, keypad STOP enabled. 04: Controlled by the RS-485 communication interface, keypad STOP disabled. Keyboard Frequency 02-15 0.00 ~ 400.00Hz 60.00 Command DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 125 0.00 to 400.00 Hz 0.00 00: Output frequency 01: Output current 02: Output voltage 03-05 Analog Output Signal 03: Output frequency command 04: Output motor speed 05: Load power factor 03-06 Analog Output Gain 01 to 200% DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 126 Attained active. 00: Always fan on 01: Power off 1 minute later, fan off 03-12 Fan Control 02: Run and fan on, stop and fan off 03: Preliminary temperature attained, Fan start to run DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 127 21: Master Frequency Selection AVI /ACI 22: Master Frequency Selection AVI/AUI 23: Operation Command Selection keypad/external 24: Auto accel/decel mode disable 25: Forced Stop (N.C.) 26: Forced Stop (N.O.) 27: Parameter lock enable 28: PID function disabled DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 128 Resolution 01: 0.1Hz Gear Ratio for Simple Index 4 ~ 1000 04-23 Function Index Angle for Simple Index 180.0 0.0 ~360.0 04-24 Function Deceleration Time for Simple 0.00 0.00 ~100.00 04-25 Index Function 8-10 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 129 Time Duration Step 12 0.0 to 65500 Sec 05-29 Time Duration Step 13 0.0 to 65500 Sec 05-30 Time Duration Step 14 0.0 to 65500 Sec 05-31 Time Duration Step 15 0.0 to 65500 Sec 8-11 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 130 VFD-B Series Factory Parameters Explanation Settings Setting 00: 1 Sec 05-32 Time Unit Settings 01: 0.1 Sec 0.00〜400.00 Hz 05-33 Skip Frequency Width 0.00 0.00〜400.00 Hz 05-34 Bias Frequency Width 0.00 8-12 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 131 10: Current exceed during Acceleration (ocA) 11: Current exceed during Deceleration (ocd) Third Most Recent 06-10 12: Current exceed during Steady State (ocn) Fault Record 13: Ground Fault (GFF) 14: Lv 15: CF1 8-13 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 132 03: Warn, after coast to stop, restart (delay 06-15 setting time) Low-Current Detection 1~600 Min. 06-15 Restart Delay Time User-Defined 220VDC~300VDC* 06-16 Low-Voltage Detection 0: Disabled Level User-Defined 06-17 Low-Voltage Detection 0.1~ 3600.0 Sec Time 06-18 Reserved 8-14 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 133 Torque Compensation Time Constant 0.01 ~10.00 Sec 0.05 0.05 ~10.00 Sec 07-13 Slip Compensation Time Constant 0.10 00 to 1439 Min. 07-14 Accumulative Motor Operation Time (Min.) 00 to 65535 Day 07-15 Accumulative Motor Operation Day 8-15 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 134 01: Starts with Minimum Output Frequency 00: Speed Search Disable 08-19 Speed Search during Start-up 01: Speed Search Enable 00: Setting Frequency Speed Search Frequency during 08-20 01: Maximum Operation Frequency Start-up (01-00) 8-16 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 135 VFD-B Series Factory Parameters Explanation Settings Setting Auto Reset Time at Restart after 00 to 60000 sec 08-21 Fault Compensation Coefficient for 00~1000 08-22 Motor Instability 8-17 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 136 03: 8,N,2 (Modbus, RTU) 04: 8,E,1 (Modbus, RTU) 05: 8,O,1 (Modbus, RTU) 09-05 HMI Register 1 00 ~ 65535 09-06 HMI Register 2 00 ~ 65535 09-07 Response Delay Time 00 ~ 200 8-18 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 137 Speed Control Output 10-14 0.00 to 10.00 Hz 10.00 Frequency Limit Sample time for refreshing 10-15 the content of 210DH and 0.01~1.00 seconds 0.10 210EH Deviation Range of PID 10-16 0.00~100.00% 100.00 Feedback Signal Error 8-19 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 138 0.0 to 3600.0 sec Auxiliary Motor Time Delay before Stopping the 11-04 0.0 to 3600.0 sec Auxiliary Motor 11-05 Sleep/Wake Up Detection Time 0.0 ~6550.0 sec 11-06 Sleep Frequency 0.00~Fmax 0.00 11-07 Wakeup Frequency 0.00~Fmax 0.00 8-20 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 139 C to 50 C without blind plate) Non-Condensing and not frozen Storage/ Transportation C to 60 Temperature Ambient Humidity Below 90% RH (non-condensing) Vibration 9.80665m/s (1G) less than 20Hz, 5.88m/s (0.6G) at 20 to 50Hz DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 140 C to 50 C without blind plate) Non-Condensing and not frozen Storage/ Transportation C to 60 Temperature Ambient Humidity Below 90% RH (non-condensing) Vibration 9.80665m/s (1G) less than 20Hz, 5.88m/s (0.6G) at 20 to 50Hz DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 141 47-63 Hz Output Voltage: Proportional to input voltage Output Frequency: 0.1 too 400Hz Max. Ambient Temp: 40 degree C (*) Enclosure: ENCLOSED Type 1 *: Max. Ambient Temp is 50 degree C for 7.5-15hp. DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 143 Output Current (A) 11.9 VFD007B21A VFD007B23A VFD015B21A/B 15.3 VFD007B43A VFD022B21A 22.0 VFD015B23A/B VFD015B43A VFD022B23A VFD022B43B VFD037B23A VFD037B43A VFD055B23A VFD055B43A VFD075B23A VFD075B43A VFD110B23A VFD110B43A VFD150B23A VFD150B43A VFD185B23A VFD185B43A VFD220B23A VFD220B43A VFD300B23A VFD300B43A VFD370B23A VFD370B43A VFD450B43A VFD550B43A VFD750B43A DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 144 VFD075B23A JJN-125 VFD075B43A JJS-70 VFD110B23A JJN-175 VFD110B43A JJS-90 VFD150B23A JJN-250 VFD150B43A JJS-125 VFD185B23A JJN-300 VFD185B43A JJS-150 VFD220B23A JJN-350 VFD220B43A JJS-175 VFD300B23A JJN-450 VFD300B43A JJS-225 VFD370B23A JJN-500 VFD370B43A JJS-250 VFD450B43A JJS-350 VFD550B43A JJS-400 VFD750B43A JJS-600 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 145 Note: Please only use DELTA resistors and recommended values. Other resistors and values will void Delta’s warranty. Please contact your nearest Delta representative for use of special resistors. For instance, in 460 V series, 100 HP, AC drive has 2 braking units with total of 16 braking resistors, so each braking unit uses 8 braking resistors.
  • Page 146 VFD-B Series Braking Resistors & Braking Units DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 147 VFD-B Series Braking Resistors & Braking Units DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 148 VFD-B Series Braking Resistors & Braking Units Braking resistors model no.: BR1K0W050, BR1K2W008, BR1K2W6P8, BR1K5W005, BR1K5W040 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 149 VFD007B23A, VFD015B23A 10TDT1W4C VFD022B23A, VFD037B23A 26TDT1W4C VFD055B23A, VFD075B23A, VFD150B43A, 50TDS4W4C VFD185B43A VFD110B23A, VFD150B23A, VFD220B43A, 100TDS84C VFD300B43A, VFD370B43A VFD550B43A, VFD750B43A 200TDDS84C VFD185B23A, VFD220B23A, VFD300B23A, 150TDS84C VFD450B43A VFD370B23A 180TDS84C VFD022B23B 20TDT1W4D VFD022B21B 35DRT1W3C VFD037B43B, VFD037B23B 26TDT1W4B4 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 150 VFD-B Series Order P/N: RF015B21AA / RF022B43AA (1.97) (1.1) (3.54) (8.9) (9.4) (8.9) (0.63) (0.94) (3.37) DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 151 VFD-B Series Order P/N: RF022B21BA / RF037B43BA DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 152 VFD-B Series Order P/N: RF110B43CA B-10 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 153 VFD-B Series Order P/N: 10TDT1W4C Order P/N: 26TDT1W4C B-11 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 154 VFD-B Series Order P/N: 50TDS4W4C Order P/N: 100TDS84C B-12 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 155 VFD-B Series Order P/N: 200TDDS84C Order P/N: 150TDS84C B-13 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 156 VFD-B Series Order P/N: 180TDS84C Order P/N: 20TDT1W4D B-14 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 157 VFD-B Series Order P/N: 26TDT1W4B4 B-15 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 158 VFD-B Series B.4 PG Card (Refer to Pr.10-10 to 10-15 of related parameter settings) Section 1 Installation 1.1) 1 to 2HP (0.75kW to 1.5kW) 1.2) 3 to 5HP (2.2kW to 3.7kW) B-16 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 159 Section 2 PG Card and Pulse Generator 2.1) Basic Wiring Diagram R/L1 R/L1 U/T1 Motor S/L2 V/T2 S/L2 T/L3 W/T3 T/L3 PG-02 +12V Factory Default Pulse Generator Output 12V DC PG-02 and Pulse Generator Connections B-17 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 160 PG-02 and Pulse Generator Connections 2.3) When Pulse Generators is Open Collector type, please refer to following wiring. R/L1 R/L1 U/T1 Motor S/L2 V/T2 S/L2 T/L3 W/T3 T/L3 PG-02 Factory Default Pulse Generator Output 5V DC B-18 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 161 E only. Recommended wire size 0.21 to 0.81mm (AWG24 to AWG18). Wire length: Types of Pulse Maximum Wire Length Wire Gauge Generators Output Voltage Open Collector 1.25mm (AWG16) or above Line Driver 300m Complementary B-19 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 162 Connect to VFD-B series control board Wiring Terminals FSW1 FSW2 PG-02 Select the power source and output of Pulse Generator 3.4) Types of Pulse Generators FSW1 and FSW2 switches Types of Pulse Generators B-20 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 163 DCM MI5 FWD REV JOG Block VFD-B Programming: Pr.02-00 set to 1 Pr.02-01 set to 1 (external controls) Pr.02-05 set to 1 (setting Run/Stop and Fwd/Rev controls) Pr.04-08 (MI5) set to 8 (External reset) B-21 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 164 VFD-B Series B.6 Remote Panel Adapter (RPA 01) Remote panel adapter for VFDPU01 VFD-PU01 Assembly figure is as following: Please refer to the following screw hole dimension according to panel thickness: B-22 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 165 Please put all wires through 4 cores in Diagram series without winding. 3.5 - 5.5 Zero Phase Reactor 8 - 14 Power R/L1 U/T1 18.5 MOTOR S/L2 V/T2 Supply T/L3 W/T3 Diagram 38 - 100 B-23 DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 167 VFD-B Series DIMENSIONS VFD007B23A 0.75 kW (1HP) 230V / 3-phase VFD007B43A 0.75 kW (1HP) 460V / 3-phase Unit: mm (inches) 145.0 [5.71] 118.0 [4.65] 108.0 [4.25] 5.5[0.22] 5.5[0.22] DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 168 VFD007B21A 0.75 kW (1HP) 230V / 1-phase VFD015B21A 1.50 kW (2HP) 230V / 1-phase VFD015B23A 1.50 kW (2HP) 230V / 3-phase VFD015B43A 1.50 kW (2HP) 460V / 3-phase Unit: mm (inches) 118.0 [4.65] 160.0 [6.30] 108.0 [4.25] 5.5[0.22] 5.5[0.22] DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 169 VFD015B21B 1.50 kW (2HP) 230V / 1-phase VFD015B23B 1.50 kW (2HP) 230V / 3-phase VFD022B23B 2.20 kW (3HP) 230V / 3-phase VFD022B43B 2.20 kW (3HP) 460V / 3-phase Unit: mm (inches) 145.0 [5.71] 118.0 [4.65] 108.0 [4.25] 5.5[0.22] 5.5[0.22] DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 170 VFD022B21A 2.20 kW (3HP) 230V / 1-phase VFD037B23A 3.70 kW (5HP) 230V / 3-phase VFD037B43A 3.70 kW (5HP) 460V / 3-phase Unit: mm (inches) 150.0 [5.91] 135.0 [5.32] 160.2 [6.31] 6.5[0.26] UNIT : mm(inch) DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 171 VFD075B23A 7.50 kW (10.0HP) 230V / 3-phase VFD075B43A 7.50 kW (10.0HP) 460V / 3-phase VFD110B23A 11.0 kW (15.0HP) 230V / 3-phase VFD110B43A 11.0 kW (15.0HP) 460V / 3-phase Unit: mm (inches) 200.0 [7.88] 185.6 [7.31] 183.2 [7.22] 7.0 [0.28] DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 172 VFD185B43A 18.5 kW (25.0HP) 460V / 3-phase VFD220B23A 22.0 kW (30.0HP) 230V / 3-phase VFD220B43A 22.0 kW (30.0HP) 460V / 3-phase Unit: mm (inches) 250.0 [9.84] 10.0 [ 0.39] 205.4 [8.08] 226.0 [8.90] 10.0 [0.39] DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 173 VFD-B Series VFD300B23A 30.0 kW (40HP) 230V / 3-phase VFD370B23A 37.0 kW (50HP) 230V / 3-phase Unit: mm (inches) 370.0 [14.57] 260.0 [10.24] 335.0 [13.19] 18.0 [0.71] 132.5 [5.22] R6.5[0.25] 13.0[0.51] DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 174 VFD300B43A 30.0 kW (40HP) 460V / 3-phase VFD370B43A 37.0 kW (50HP) 460V / 3-phase VFD450B43A 45.0 kW (60HP) 460V / 3-phase Unit: mm (inches) 370.0 [14.57] 260.0 [10.24] 335.0 [13.19] 18.0 [0.71] 132.5 [5.22] R6.5[0.25] 13.0[0.51] DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 175 VFD-B Series VFD550B43A 55.0 kW (75HP) 460V / 3-phase VFD750B43A 75.0 kW (100HP) 460V / 3-phase Unit: mm (inches) 425.0 [16.73] 264.0 [10.39] 385.0 [15.16] 18.0 [0.71] 130.4 [5.13] 280.0 [11.02] R6.5[0.25] 13.0[0.51] DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 177 Amendment Directive 93/68/EEC. For the evaluation of the compliance with this Directive, the following standard was applied: EN 50178 The following manufacturer/importer is responsible for this declaration: Delta Electronics, Inc. (Company Name) DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...
  • Page 178 Directive 93/68/EEC. For the evaluation of the compliance with this Directive, the following standard was applied: EN61800-3, EN55011, EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-8 The following manufacturer/importer is responsible for this declaration: Delta Electronics, Inc. (Company Name) DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED...