Delta C2000 series User Manual page 119

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Chapter 8 Optional Cards |C2000 Series
EMC-D42A
I/O Extension
Card
MO10~MO11
EMC-D611A
I/O Extension
Card
EMC-R6AA
Relay Extension
R10A~R15A
Card
R10C~R15C
Terminals
Common for Multi-function input terminals
COM
Select SINK (NPN) /SOURCE (PNP) in J1 jumper / external power
supply
Refer to parameters 02-26~02-29 to program the multi-function
inputs MI10~MI13.
Internal power is applied from terminal E24: +24Vdc±5% 200mA,
5W
MI10~ MI13
External power +24VDC: max. voltage 30VDC, min. voltage
19VDC, 30W
ON: the activation current is 6.5mA
OFF: leakage current tolerance is 10μA
Multi-function output terminals (photocoupler)
Duty-cycle: 50%
Max. output frequency: 100Hz
Max. current: 50mA
Max. voltage: 48Vdc
Common for multi-function output terminals MO10,
MO11(photocoupler)
MXM
Max 48VDC 50mA
Terminals
AC
AC power Common for multi-function input terminal (Neutral)
Refer to Pr. 02.26~ Pr. 02.31 for multi-function input selection
Input voltage: 100~130VAC
Input frequency: 57~63Hz
MI10~ MI15
Input impedance: 27Kohm
Terminal response time:
ON: 10ms
OFF: 20ms
Terminals
Refer to Pr. 02.36~ Pr. 02.41 for multi-function input selection
Resistive load:
5A(N.O.)/3A 250VAC
5A(N.O.)/3A 30VDC
Inductive load (COS 0.4)
2.0A(N.O.)/1.2A 250VAC
2.0A(N.O.)/1.2A 30VDC
It is used to output each monitor signal, such as drive is in
operation, frequency attained or overload indication.
Descriptions
Descriptions
Descriptions
8-4