Chapter 12 Description of Parameter Settings|C2000 Series
a shorter time constant.
Top Limit of Frequency Deviation
Settings 0.00~100.00Hz
Pr.10-29 is for setting the maximum of frequency deviation.
Resolver Pole Pair
Settings 1~50
To use Pr.10-30 function, user must set Pr.10-00=3(Resolver Encoder) first.
Reserved
Reserved
Reserved
Reserved
I/F Mode, current command
Settings
PM Sensorless Obeserver Bandwith for High Speed Zone
Settings 0.00~600.00Hz
PM Sensorless Observer Low-pass Filter Gain
Settings 0.00~655.35Hz
PM Sensorless Control Word
Settings 0000~FFFFh
Bit No.
0
Reserved
1
Reserved
2
Choose a control mode to
statrt.
3
Choose a mode to stop .
4
Reserved
5
Choose a control mode to stop 0 : When lower than Pr10-40, coast to stop
6
Reserved
7
Reserved
Frequency Point when switch from I/F mode to PM Sensorless mode
0~150%Irated (
Rated current % of the drive
Function
0 :Start by IF mode
1: Start by VF mode
0 :Stop by IF mode
1 :Stop by VF mode
If lower than Pr10-40, decelerate to stop by VF mode.
)
Description
12-156
Factory Setting: 20.00
Factory Setting: 1
Factory Setting: 40
Factory Setting: 5.00
Factory Setting: 1.00
Factory Setting: 0000