Delta C2000 series User Manual page 388

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Fault Name
Fault
CC (current clamp)
Hd0
cc HW error
Fault
OC hardware error
Hd1
Oc HW error
Fault
OV hardware error
Hd2
Ov HW error
Fault
Occ hardware error
Hd3
occ HW error
Fault
Auto tuning error
AUE
Auto tuning err
Fault
PID loss (ACI)
AFE
PID Fbk error
Fault
PG feedback error
PGF1
PG Fbk error
Fault
PG feedback loss
PGF2
PG Fbk loss
Fault
PG feedback stall
PGF3
PG Fbk over SPD
Fault
PG slip error
PGF4
PG Fbk deviate
Fault Descriptions
Chapter 14 Fault Codes and Descriptions |C2000 Series
Corrective Actions
Reboots the power. If fault code is still displayed on the
keypad please return to the factory
Reboots the power. If fault code is still displayed on the
keypad please return to the factory
Reboots the power. If fault code is still displayed on the
keypad please return to the factory
Reboots the power. If fault code is still displayed on the
keypad please return to the factory
1. Check cabling between drive and motor
2. Try again.
1.
Check the wiring of the PID feedback
2.
Check the PID parameters settings
Check if encoder parameter setting is accurate when
it is PG feedback control.
Check the wiring of the PG feedback
1.
Check the wiring of the PG feedback
2.
Check if the setting of PI gain and deceleration is
suitable
3.
Return to the factory
1.
Check the wiring of the PG feedback
2.
Check if the setting of PI gain and deceleration
is suitable
3.
Return to the factory
14-5