Chapter 11 Summary of Parameter Settings|C2000 Series

07 Special Parameters

Pr.
Explanation
07-00
Software Brake Level
07-01
DC Brake Current Level
07-02
DC Brake Time at Start-up
07-03
DC Brake Time at Stop
07-04
Startup Frequency for DC Brake
07-05
Maximum Power Loss Duration
Restart after Momentary Power
07-06
Loss
07-07
Maximum Power Loss Duration
07-08
Base Block Time
07-09
Current Limit for Speed Search
07-10
Treatment to Reboots After Fault
07-11
Auto Restart After Fault
07-12
Speed Search during Start-up
Decel. Time to Momentary
07-13
Power Loss
07-14
DEB Return Time
07-15
Dwell Time at Accel.
07-16
Dwell Frequency at Accel.
07-17
Dwell Time at Decel.
07-18
Dwell Frequency at Decel.
07-19
Fan Cooling Control
Emergency Stop (EF) & Force to
07-20
Stop Selection
Settings
230V: 350.0~450.0Vdc
460V: 700.0~900.0Vdc
0~100%
0.0~60.0 sec.
0.0~60.0 sec.
0.00~600.00Hz
1~200%
0: Stop operation
1: Speed search for last frequency command
2: Speed search for minimum output frequency
0.1~20.0 sec.
0.1~5.0 sec.
20~200%
0: Stop operation
1: Speed search starts with current speed
2: Speed search starts with minimum output frequency
0~10
0: Disable
1: Speed search for maximum output frequency
2: Speed search for start-up motor frequency
3: Speed search for minimum output frequency
0: Disable
1: 1st decel. time
2: 2nd decel. time
3: 3rd decel. time
4: 4th decel. time
5: current decel. time
6: Auto decel. time
0.0~25.0sec
0.00 ~ 600.00sec
0.00 ~ 600.00Hz
0.00 ~ 600.00sec
0.00 ~ 600.00Hz
0: Fan always ON
1: 1 minute after the AC motor drive stops, fan will be
OFF
2: When the AC motor drive runs, the fan is ON. When
the AC motor drive stops, the fan is OFF
3: Fan turns ON when preliminary heat sink
temperature (around 60
4: Fan always OFF
0: Coast stop
1: By deceleration Time 1
2: By deceleration Time 2
3: By deceleration Time 3
4: By deceleration Time 4
5: System Deceleration
6: Automatic Deceleration
11-24
o
C) is attained.
Factory
Setting
380.0
760.0
0
0.0
0.0
0.00
100
0
2.0
0.5
50
0
0
0
0
0.0
0.00
0.00
0.00
0.00
0
0