Reserve
Analog Input Curve Selection
Settings 0: Regular Curve
1: 3 point curve of AVI
2: 3 point curve of ACI
3: 3 point curve of AVI & ACI
4: 3 point curve of AUI
5: 3 point curve of AVI & AUI
6: 3 point curve of ACI & AUI
7: 3 point curve of AVI & ACI & AUI
AVI Low Point
Settings 03-28=0, 0.00~10.00V
03-28≠0, 0.00~20.00mA
AVI Proportional Low Point
Settings 0.00~100.00%
AVI Mid Point
Settings 03-28=0, 0.00~10.00V
03-28≠0, 0.00~20.00mA
AVI Proportional Mid Point
Settings 0.00~100.00%
AVI High Point
Settings 03-28=0, 0.00~10.00V
03-28≠0, 0.00~20.00mA
AVI Proportional High Point
Settings 0.00~100.00%
When Pr.03-28 = 0, AVI setting is 0-10V and the unit is in voltage (V).
When Pr.03-28 ≠ 0, AVI setting is 0-20mA or 4-20mA and the unit is in current (mA).
When setting anaolog input AVI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency).
Three of the AVI points can be set according to user's demand on voltage(current) and proportion,
Chapter 12 Description of Parameter Settings|C2000 Series
12-77
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 5.00
Factory Setting: 50.00
Factory Setting: 10.00
Factory Setting: 100.00