Motor Parameters - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

05 Motor Parameters

Pr.
Explanation
05-00
Motor Auto Tuning
Full-load Current of Induction
05-01
Motor 1(A)
Rated Power of Induction Motor
05-02
1(kW)
Rated Speed of Induction Motor
05-03
1 (rpm)
Pole Number of Induction Motor
05-04
1
No-load Current of Induction
05-05
Motor 1 (A)
Stator Resistance (Rs) of
05-06
Induction Motor 1
Rotor Resistance (Rr) of
05-07
Induction Motor 1
Magnetizing Inductance (Lm) of
05-08
Induction Motor 1
Stator Inductance (Lx) of
05-09
Induction Motor 1
05-10
Reserved
~
05-12
Full-load Current of Induction
05-13
Motor 2 (A)
Rated Power of Induction Motor
05-14
2 (kW)
Rated Speed of Induction Motor
05-15
2 (rpm)
Pole Number of Induction Motor
05-16
2
No-load Current of Induction
05-17
Motor 2 (A)
Stator Resistance (Rs) of
05-18
Induction Motor 2
Rotor Resistance (Rr) of
05-19
Induction Motor 2
Magnetizing Inductance (Lm) of
05-20
Induction Motor 2
Stator Inductance (Lx) of
05-21
Induction Motor 2
05-22
Induction Motor 1/ 2 Selection
Frequency for
05-23
Y-connection/△-connection
Switch of Induction Motor
Y-connection/△-connection
05-24
Switch of Induction Motor
Chapter 11 Summary of Parameter Settings|C2000 Series
Settings
0: No function
1: Rolling test for induction motor(IM) (Rs, Rr, Lm, Lx,
no-load current)
2: Static test for induction motor(IM)
3: No function
4: Rolling test for PM motor magnetic pole
5: Rolling test for PM motor
6: Rolling test for IM motor flux curve
12: FOC Sensorless inertia estimation
13: High frequency and blocked rotor test for PM motor
10~120% of drive's rated current
0~655.35kW
0~65535
1710(60Hz 4poles) ; 1410(50Hz 4 poles)
2~20
0~ Pr.05-01 factory setting
0~65.535Ω
0~65.535Ω
0~6553.5mH
0~6553.5mH
10~120%
0~655.35kW
0~65535
1710(60Hz 4 poles) ; 1410(50Hz 4 poles)
2~20
0~ Pr.05-01 factory setting
0~65.535Ω
0~65.535Ω
0~6553.5mH
0~6553.5mH
1: motor 1
2: motor 2
0.00~600.00Hz
0: Disable
1: Enable
11-17
Factory
Setting
0
#.##
#.##
1710
4
#.##
#.###
#.###
#.#
#.#
#.##
#.##
1710
4
#.##
#.###
#.###
#.#
#.#
1
60.00
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents