Chapter 12 Description of Parameter Settings|C2000 Series
Filter Time for PID Feedback
Settings 0.1~300.0 sec
When the PID control function is normal, it should calculate within a period of time and close to the
setpoint value.
Refer to the PID control diagram for details. When executing PID feedback control, if |PID
reference target value – detection value| > Pr.08-13 PID Deviation Level and exceeds Pr.08-14
setting, the PID control fault occurs. The treatment will be done as Pr.08-09 setting.
PID Compensation Selection
Settings 0: Parameter setting
PID Compensation
Settings -100.0~+100.0%
Setting of Sleep Mode Function
Settings
Wake-up Integral Limit
Settings 0.0~200.0%
Enable PID to Change the Operation Direction
Settings
1: Analog input
0: Follow PID output command
1: Follow PID feedback signal
0: Disable change of direction
1: Enable change of direction
12-132
Factory Setting: 5.0
Factory Setting: 0
Factory Setting: 0
Factory Setting: 0
Factory Setting: 50.0
Factory Setting: 0