Delta C2000 series User Manual page 177

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Chapter 11 Summary of Parameter Settings|C2000 Series
Pr.
Source of the Operation Command
00-21
(AUTO)
00-22
Stop Method
00-23
Control of Motor Direction
00-24
Memory of Frequency Command
00-25
User Defined Characteristics
00-26
Max. User Defined Value
00-27
User Defined Value
00-28
Reserved
00-29
LOCAL/REMOTE Selection
Source of the Master Frequency
00-30
Command(HAND)
Explanation
Settings
3: External UP/DOWN terminal
4: Pulse input without direction command (Pr.10-16
without direction)
5: Pulse input with direction command (Pr.10-16)
6: CANopen communication card
7: Reserved
8: Communication card (no CANopen card)
0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP
disabled.
3: CANopen communication card
4: Reserved
5: Communication card (no CANopen card)
0: Ramp to stop
1: Coast to stop
0: Enable forward/reverse
1: Reverse disable
2: Forward disable
Read only
Bit 0~3: user define on decimal place
0000b: no decimal place
0001b: one decimal place
0010b: two decimal place
0011b: three decimal place
Bit 4~15: user define on unit
000xh: Hz
001xh: rpm
002xh: %
003xh: kg
0: Disable
0~65535 (when Pr.00-25 set to no decimal place)
0.0~6553.5 (when Pr.00-25 set to 1 decimal place)
0.0~655.35 (when Pr.00-25 set to 2 decimal place)
0.0~65.535 (when Pr.00-25 set to 3 decimal place)
Read only
0: Standard HOA function
1: Switching Local/Remote, the drive stops
2: Swithcing Local/Remote, the drive runs as the
REMOTE setting for frequency and operation
status
3: Swithcing Local/Remote, the drive runs as the
LOCAL setting for frequency and operation status
4: Swithcing Local/Remote, the drive runs as
LOCAL setting when switch to Local and runs as
REMOTE setting when switch to Remote for
frequency and operation status.
0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
4: Pulse input without direction command (Pr.10-16
without direction)
5: Pulse input with direction command (Pr.10-16)
6: CANopen communication card
7: Reserved
8: Communication card (no CANopen card)
11-4
Factory
Setting
0
0
0
Read
only
0
0
Read
Only
0
0

Hide quick links: