Group 9: Communication Parameters

Communication Address

09 - 00
Settings
If the AC drive is controlled by RS-485 serial communication, the communication
address for this drive must be set via this parameter.
09 - 01

Transmission Speed

Settings
Users can set parameters and control the operation of the AC drive via the RS-485
serial interface of a personal computer. This parameter is used to set the transmission
speed between the computer and AC drive.
09 - 02

Transmission Fault Treatment

Settings
This parameter is set to detect if an error occurs and take actions.
09 - 03
Time Out Detection
Settings
09 - 04
Communication Protocol
Settings
1. Computer Control
01 to 254
00
Baud rate 4800 (data transmission speed: bits / second)
01
Baud rate 9600 (data transmission speed: bits / second)
02
Baud rate 19200 (data transmission speed: bits / second)
03
Baud rate 38400 (data transmission speed: bits / second)
00
Warn and keep operating
01
Warn and RAMP to stop
02
Warn and COAST to stop
03
No warning and keep operating
0.0
Disable
0.0 ~ 60.0 sec
00
Modbus ASCII mode, protocol <7,N,2>
01
Modbus ASCII mode, protocol <7,E,1>
02
Modbus ASCII mode, protocol <7,O,1>
03
Modbus RTU mode, protocol <8,N,2>
04
Modbus RTU mode, protocol <8,E,1>
05
Modbus RTU mode, protocol <8,O,1>
5-54
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Factory Setting: 01
Factory Setting: 01
Factory Setting: 03
Factory Setting: 0.0
Unit: 1
Factory Setting: 00