03 Analog Input/Output Parameter

Analog Input Selection (AVI)
Analog Input Selection (ACI)
Analog Input Selection (AUI)
Settings
0: No function
1: Frequency command (torque limit under torque control mode)
2: Torque command (torque limit under speed mode)
3: Torque compensation command
4: PID target value
5: PID feedback signal
6: PTC thermistor input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive/negative torque limit
11: PT100 thermistor input value
12~17: Reserved
When it is frequency command or TQC speed limit, the corresponding value for 0~±10V/4~20mA is
0 – max. output frequency(Pr.01-00)
When it is torque command or torque limit, the corresponding value for 0~±10V/4~20mA is 0 – max.
output torque (Pr.11-27).
When it is torque compensation, the corresponding value for 0~±10V/4~20mA is 0 – rated torque.
03-00~02=9
Regenerative
torque limit
03-00~02=10
Positive/negative torque limit
Reverse
03-00~02=10
Positive/negative torque limit
03-00~02=8
Negative torque limit
Analog Input Bias (AVI)
Settings -100.0~100.0%
Chapter 12 Description of Parameter Settings|C2000 Series
This parameter can be set during operation.
Positive torque
Negative Torque
12-55
Factory Setting: 1
Factory Setting: 0
Factory Setting: 0
03-00~02=7
Positive torque limit
Forward
03-00~02=9
Regenerative
torque limit
Factory Setting: 0