Chapter 12 Description of Parameter Settings|C2000 Series
as 0 (the torque mode), if torque command is 0%, the motor will produce excitation current but no
torque current. When Pr.11-39 is set as 1 (the speed mode), if torque command is 0%, the AC
motor drive can still produce torque current through speed controller to prevent motor race and
the drive will also atomatically adjust the speed to 0 when the speed command is not equal to 0.

Command Source of Point-to-Point Position Control

Settings
Reserved
系統控制旗標
Settings 0000~FFFFh
Bit No.
0
At torque mode, selection between
speed control and current control.
1
FWD/REV direction control
2
Fuzzy PID selection control
3~15 Reserved
Max. Frequency of Point- to-Point Position Control
Settings 0.00~327.67Hz
Accel. Time of Point-to Point Position Control
Settings 0.00~655.35sec
Decel. Time of Point-to Point Position Control
Settings 0.00~655.35sec
0: External terminal
1: Reserved
2: RS485
3: CAN
4: PLC
5: Communication card
Function
Description
0:Speed control at torque mode, the largest current
limit is the torque command.
1: Speed control at torque mode, P06-12 the largest
current limit is Pr06-12
0: FWD/REV cannot be controlled by 02-12 bit 0 & 1
1: FWD/REV can be controlled by 02-12 bit 0&1
0: Fuzzy PID enabled
1: Fuzzy PID disabled
12-168
Factory Settings:0
Factory Settings: 0000
Factory Settings:10.00
Factory Settings:1.00
Factory Settings:3.00