AC Reactor

When the AC Motor Drive is connected directly to a large-capacity power transformer (600kVA or
above) or when a phase lead capacitor is switched, excess peak currents may occur in the power
input circuit due to the load changes and the converter section may be damaged. To avoid this, it is
recommend to use a serial connected AC input reactor(6%) at the AC Motor Drive mains input side
to reduce the current and improve the input power efficiency.
230V, 50/60Hz, 3-phase
kW
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
460V, 50/60Hz, 3-phase
kW
0.75
1.5
2.2
3.7
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
185
220
280
315
355
Rated Amps of AC
HP
Reactor
1
4
2
8
3
12
5
18
7.5
25
10
35
15
45
20
55
25
80
30
100
40
130
50
160
60
200
75
250
100
320
125
400
Rated Amps of AC
HP
Reactor
1
4
2
4
3
8
5
12
5
12
7.5
18
10
18
15
25
20
35
25
45
30
45
40
80
50
80
60
100
75
130
100
160
125
200
150
250
175
320
215
400
250
400
300
500
375
600
425
750
475
750
Chapter 7 Optional Accessories|C2000 Series
Max. continuous
Amps
6
12
18
27
37.5
52.5
67.5
82.5
120
150
195
240
300
375
480
600
Max. continuous
Amps
6
6
12
18
18
27
27
37.5
52.5
67.5
67.5
120
120
150
195
240
300
375
480
600
600
750
900
1125
1125
7-7
Inductance(mh)
3% impedance 5% impedance
3
6.5
1.5
3
1.25
2.5
0.8
1.5
0.5
1.2
0.4
0.8
0.3
0.7
0.25
0.5
0.2
0.4
0.15
0.3
0.1
0.2
0.075
0.15
0.055
0.110
0.090
0.150
0.040
0.075
0.03
0.006
Inductance(mh)
3% impedance 5% impedance
9
12
6.5
9
5
7.5
2.5
4.2
2.5
4.2
1.5
2.5
1.5
2.5
1.2
2
0.8
1.2
0.7
1.2
0.7
1.2
0.4
0.7
0.4
0.7
0.3
0.45
0.2
0.3
0.15
0.23
0.110
0.185
0.090
0.150
0.075
0.125
0.03
0.06
0.03
0.06
0.025
0.05
0.02
0.04
0.029
0.048
0.029
0.048

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents