Wiring Precautions - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Wiring precautions:

Reserves 5mm and properly install the wire into the terminal; fasten the installation by a
slotted screwdriver. If the wire is stripped, sort the wire before install into the terminal.
Flathead screwdriver: blade width 3.5mm, tip thickness 0.6mm
In the figure above, the factory setting for S1-SCM is short circuit. The factory setting for
+24V-COM is short circuit and SINK mode (NPN); please refer to Chapter 4 Wiring for more
detail.
Terminals
Terminal Function
Digital control signal common
+24V
(Source)
Digital control signal common
COM
(Sink)
FWD
Forward-Stop command
REV
Reverse-Stop command
MI1
~
Multi-function input 1~8
MI8
Digital frequency meter
DFM
DCM
Digital frequency signal common
Multi-function Output 1
MO1
(photocoupler)
Multi-function Output 2
MO2
(photocoupler)
MCM
Multi-function Output Common
Multi-function relay output 1
RA1
(N.O.) a
Multi-function relay output 1
RB1
(N.C.) b
Multi-function relay common
RC1
Multi-function relay output 2
RA2
(N.O.) a
Multi-function relay output 2
RB2
(N.C.) b
Multi-function relay common
RC2
Potentiometer power supply
+10V
Factory Setting (NPN mode)
+24V±5% 200mA
Common for multi-function input terminals
FWD-DCM:
ON
forward running
OFF
deceleration to stop
REV-DCM:
ON
reverse running
OFF
deceleration to stop
Refer to parameters 02-01~02-08 to program the
multi-function inputs MI1~MI8.
ON: the activation current is 6.5mA 11Vdc
OFF: leakage current tolerance is 10μA 11Vdc
Regard the pulse voltage as the output monitor
signal
DFM
Duty-cycle: 50%
Min. load impedance: 1kΩ/100pf
DCM
Max. current: 30mA
Max. voltage: 30Vdc
The AC motor drive releases various monitor
signals, such as drive in operation, frequency
attained and overload indication, via transistor (open
collector).
Max 48Vdc 50mA
Resistive Load:
5A(N.O.)/3A(N.C.) 250VAC
5A(N.O.)/3A(N.C.) 30VDC
Inductive Load (COS 0.4):
2.0A(N.O.)/1.2A(N.C.) 250VAC
2.0A(N.O.)/1.2A(N.C.) 30VDC
It is used to output each monitor signal, such as
drive is in operation, frequency attained or overload
indication.
Analog frequency setting: +10Vdc 20mA
6-3
Chapter 6 Control Terminals|C2000 Series
MO1
MO2
MCM