Address List - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Chapter 12 Description of Parameter Settings|C2000 Series

3. Address list

Content
AC drive Parameters GGnnH
Command
Write only
Command
Write only
Status monitor
Read only
Address
GG means parameter group, nn means parameter number, for
example, the address of Pr 4-01 is 0401H.
2000H
Bit 0-3
Bit 4-5
Bit 6-7
Bit 8-11
Bit 12
Bit 13~14 00B: No function
Bit 15
2001H
Frequency command
Bit 0
Bit 1
2002H
Bit 2
Bit 3-15
Error code: refer to Pr.06-17 to Pr.06-22
2100H
AC Drive Operation Status
2101H
Bit0
00b: Drive stops
01b: Drive decelerating
Bit1
10b: Drive standby
Bit2
Operation Direction
Bit3
00b: FWD run
01b: from REV run to FWD run
Bit4
10b: REV run
11b: from FWD run to REV run
Bit8
12-140
Function
0: No function
1: Stop
2: Run
3: Jog + Run
00B: No function
01B: FWD
10B: REV
11B: Change direction
00B: 1st accel/decel
01B: 2nd accel/decel
10B: 3rd accel/decel
11B: 4th accel/decel
000B: master speed
0001B: 1st accel/decel.
0010B: 2nd accel/decel
0011B: 3rd accel/decel
0100B: 4th accel/decel
0101B: 5th accel/decel
0110B: 6th accel/decel
0111B: 7th accel/decel
1000B: 8th accel/decel
1001B: 9th accel/decel
1010B: 10th accel/decel
1011B: 11th accel/decel
1100B: 12th accel/decel
1101B: 13th accel/decel
1110B: 14th accel/decel
1111B: 15th accel/decel
1: enable bit06-11 function
01B: operated by digital keypad
10B: operated by Pr.00-21 setting
11B: change operation source
Reserved
1: EF (external fault) on
1: Reset
1: B.B. ON
Reserved
11b: Drive operating
1: JOG Command
1: Master frequency controlled by communication
interface

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents