09 Communication Parameters

Pr.
Explanation
09-00
COM1 Communication Address
09-01
COM1 Transmission Speed
COM1 Transmission Fault
09-02
Treatment
09-03
COM1 Time-out Detection
09-04
COM1 Communication Protocol
09-05
~
Reserved
09-08
09-09
Response Delay Time
Main Frequency of the
09-10
Communication
09-11
Block Transfer 1
09-12
Block Transfer 2
09-13
Block Transfer 3
09-14
Block Transfer 4
09-15
Block Transfer 5
09-16
Block Transfer 6
09-17
Block Transfer 7
09-18
Block Transfer 8
09-19
Block Transfer 9
09-20
Block Transfer 10
09-21
Block Transfer 11
09-22
Block Transfer 12
09-23
Block Transfer 13
09-24
Block Transfer 14
09-25
Block Transfer 15
09-26
Block Transfer 16
Chapter 11 Summary of Parameter Settings|C2000 Series
Settings
1~254
4.8~115.2Kbps
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
0.0~100.0 sec.
1: 7N2 (ASCII)
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
9: 8O1 (ASCII)
10: 8E2 (ASCII)
11: 8O2 (ASCII)
12: 8N1 (RTU)
13: 8N2 (RTU)
14: 8E1 (RTU)
15: 8O1 (RTU)
16: 8E2 (RTU)
17: 8O2 (RTU)
0.0~200.0ms
0.00~600.00Hz
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
0~65535
11-27
Factory
Setting
1
9.6
3
0.0
1
2.0
60.00
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0