Delta C2000 series User Manual page 183

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Chapter 11 Summary of Parameter Settings|C2000 Series
Pr.
Explanation
02-18
Multi-function output direction
Terminal counting value attained
02-19
(returns to 0)
Preliminary counting value
02-20
attained (not return to 0)
02-21
Digital Output Gain (DFM)
02-22
Desired Frequency Attained 1
The Width of the Desired
02-23
Frequency Attained 1
02-24
Desired Frequency Attained 2
The Width of the Desired
02-25
Frequency Attained 2
02-32
Brake Delay Time
Output Current Level Setting for
02-33
Multi-function External Terminals
Output frequency setting
02-34
for multi-function output
terminal
External Operation Control
02-35
Selection after Reset and
Settings
18: Preliminary count value attained, returns to 0
(Pr.02-19)
19: Base Block
20: Warning output
21: Over voltage warning
22: Over-current stall prevention warning
23: Over-voltage stall prevention warning
24: Operation mode indication
25: Forward command
26: Reverse command
27: Output when current >= Pr.02-33 (>= 02-33)
28: Output when current <=Pr.02-33(<= 02-33)
29: Output when frequency >= Pr.02-34 (>= 02-34)
30: Output when frequency <= Pr.02-34 (<= 02-34)
31: Y-connection for the motor coil
32: △-connection for the motor coil
33: Zero speed (actual output frequency)
34: Zero speed include stop(actual output frequency)
35: Error output selection 1(Pr.06-23)
36: Error output selection 2(Pr.06-24)
37: Error output selection 3(Pr.06-25)
38: Error output selection 4(Pr.06-26)
39: Position attained (Pr.10-19)
40: Speed attained (including Stop)
41: Multi-position attained
42: Crane function
43: Actual motor speed slower than Pr.02-47
44: Low current output (use with Pr.06-71~06-73)
45: UVW Output Electromagnetic valve Switch
46: Master dEb warning output
47: Closed brake output
48: Reserved
49: Homing action complete
50: Output for CANopen control
51: Output for communication card
52: Output for RS485
53~62: Reserved
0000h~FFFFh (0: N.O.; 1: N.C.)
0~65500
0~65500
1~166
0.00~600.00Hz
0.00~600.00Hz
0.00~600.00Hz
0.00~600.00Hz
0.000~65.000 sec.
0~100%
0.00~600.00Hz(Motor speed when using PG Card)
0: Disable
11-10
Factory
Setting
0000
0
0
1
60.00/
50.00
2.00
60.00/
50.00
2.00
0.000
0
0.00
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents