Delta C2000 series User Manual page 62

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Frame G
Main circuit terminals:
R/L11, R/L12, S/L21, S/L22, T/L31, T/L32
Max. Wire
Models
Gauge
VFD1850C43A
VFD2200C43A
300MCM*4
(152mm
VFD1850C43E
VFD2200C43E
Main circuit terminals:
U/T1, V/T2, W/T3, +1/DC+, -/DC-
Max. Wire
Models
Gauge
VFD1850C43A
VFD2200C43A
500MCM*2
(253mm
VFD1850C43E
VFD2200C43E
1.
UL installations must use 600V, 75
wire only.
2.
Use 600V, 90 wire
temperature is over 45℃.
3.
Figure 1 and Figure 2 show the specification for using ring lug.
4.
Specification for grounding wire
Torque: M8 180kg-cm (156 lb-in.) (17.64Nm)
in Figure 1
5.
Figure 3 and Figure 4 shows the specification of insulated heat
shrink tubing that comply with UL (600C, YDPU2).
Figure 1
R/L11,
R/L12,
S/L21,
T/L31, T/L32,
31MAX.
26.5MAX.
Figure 3
5-11
Chapter 5 Main Circuit Terminals|C2000 Series
Min. Wire Gauge
2/0AWG*4 (67.4mm
3/0AWG*4 (85mm
2
*4)
1/0AWG*4 (53.5mm
2/0AWG*4 (67.4mm
Min. Wire Gauge
400MCM*2 (203mm
500MCM*2 (253mm
2
*2)
300MCM*2 (152mm
400MCM*2 (203mm
or 90
for VFD2200C43A when the surrounding
: 300MCM*4 [152 mm
Figure2
S/L22,
U/T1, V/T2, W/T3, +1/DC+, -/DC-
42.0(MAX.)
Figure 4
Torque
(±10%)
2
*4)
M8
2
*4)
200kg-cm
(173 lb-in.)
2
*4)
(19.62Nm)
2
*4)
Torque
(±10%)
2
*2)
M12
2
*2)
408kg-cm
(354lb-in.)
2
*2)
( 40Nm)
2
*2)
℃ wire. Use copper
2
*2]
, as shown
(±10%)
42.0(MAX.)

Hide quick links: