Multi-Function Output Direction; Terminal Counting Value Attained (Return To 0) - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Example: Crane Application
multi-function ou tput
MO=42 (Active when
Fcom>=02 -34, outp ut
current>02-33 and time
>02-32 )
It is recommended to be used with Dwell function as shown in the following:
Multi-function output
MO= 42
( Activate when
Fcmd >= 02-34
output current > 02-33
Time > 02-32)

Multi-function Output Direction

Settings
The setting of this parameter is in hexadecimal.
This parameter is set via bit setting. If a bit is 1, the corresponding output acts in the opposite way.
Example:
If Pr02-13=1 and Pr02-18=0, Relay 1 is ON when the drive runs and is open when the drive is
stopped.
If Pr02-13=1 and Pr02-18=1, Relay 1 is open when the drive runs and is closed when the drive is
stopped.
Bit setting
bit15 bit14 bit13 bit12 bit11 bit10
MO20 MO19 MO18 MO17 MO16 MO15 MO14 MO13 MO12 MO11 MO10 MO2 MO1 Reserved RY2 RY1

Terminal Counting Value Attained (return to 0)

Settings 0~65535
The counter trigger can be set by the multi-function terminal MI6 (set Pr.02-06 to 23). Upon
completion of counting, the specified output terminal will be activated (Pr.02-13~02-14, Pr.02-36,
02-37 is set to 18). Pr.02-19 can't be set to 0.
Output
Frequency
Freq. Co mman d>02-34
& output cu rre nt >02 -33
Set 07-16=02-34and
output current >02-33
07-16 Dwell
Freq.
at Accel.
Output Freq.
0000h~FFFFh(0:N.O. ; 1:N.C.)
bit9
Chapter 12 Description of Parameter Settings|C2000 Series
02-32
Set 07-18=02-34 and
output current <02-57
07-15
Dwell Time at Accel.
02-32
Brake Delay Time
bit8
bit7
bit6
12-46
Freq. command<02 -58
or o utput current <02-57
02 -32
07-18 Dwell Freq.
at Decel.
07-17
Dwell Time atDecel.
02-32
Brake Delay Time
Factory Setting: 0000
bit5
bit4
bit3
bit2
Factory Setting: 0
bit1 bit0