Parameter Protection Password Input; Parameter Protection Password Setting - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Software Version
Settings Read only

Parameter Protection Password Input

Settings 1~9998, 10000~65535
Display
This parameter allows user to enter their password (which is set in Pr.00-08) to unlock the
parameter protection and to make changes to the parameter.
Pr.00-07 and Pr.00-08 are used to prevent the personal misoperation.
When the user have forgotten the password, clear the setting by input 9999 and press ENTER key,
then input 9999 again and press Enter within 10 seconds. After decoding, all the settings will
return to factory setting.

Parameter Protection Password Setting

Settings 1~9998, 10000~65535
To set a password to protect your parameter settings.If the display shows 0, no password is set
nor password has been correctly entered in Pr.00-07. All parameters can then be changed,
including Pr.00-08. The first time you can set a password directly. After successful setting of
password the display will show 1. Be sure to write down the password for later use. To cancel the
parameter lock, set the parameter to 0 after inputting correct password into Pr. 00-07.
How to retrieve parameter protection after decoding by Pr.00-07:
Method 1: Re-enter the password to Pr.00-08 (input the password once).
Method 2: After reboots, password function will be recovered.
Method 3: Input any value into Pr.00-07 (Do not enter the password).
.
Password Decode Flow Chart
Pass word Setting
00-08
Displays 01 afte r
correct passwo rd is
entered to Pr.00 -08.
0~3 (the times of password attempts)
0: No password protection / password is entered correctly (Pr00-07)
1: Password has been set
Pass word Forgotten
00-07
Enter 9999 and press ENTER,
then ente r 9999 aga in withi n 10
se cond s an d pre ss ENTER.
Then all pa ra meters will re set
to factory se ttings.
Chapter 12 Description of Parameter Settings|C2000 Series
Pass word Incor rect
3 chan ces of p assword inpu t:
Incorre ct p ass word 1:
Incorre ct p ass word 2:
Incorre ct p ass word 3: "Pcode "(blin king)
Keyp ad will be locked after 3 wrong attemp ted
pas swords. To re-activate t he k eypa d, please
reboo t the drive an d in put t he correct
pas sword.
12-5
Factory Setting: #.#
Factory Setting: 0
Factory Setting: 0
00-07
d isplays "01"