Upper Limit Of Integral Control; Pid Output Frequency Limit; Pid Mode Selection - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

recommended to use this function in the serious interference.

Upper limit of Integral Control

Settings 0.0~100.0%
This parameter defines an upper bound or limit for the integral gain (I) and therefore limits the
Master Frequency. The formula is: Integral upper bound = Maximum Output Frequency (Pr.01-00)
x (Pr.08-04 %).
Too large integral value will make the slow response due to sudden load change. In this way, it
may cause motor stall or machine damage.

PID Output Frequency Limit

Settings 0.0~110.0%
This parameter defines the percentage of output frequency limit during the PID control. The formula
is Output Frequency Limit = Maximum Output Frequency (Pr.01-00) X Pr.08-05 %.
PID feedback value by communication protocol
Settings 0.00~200.00%
PID Delay Time
Settings
0.0~35.0 sec

PID Mode Selection

Settings
0: Serial connection
1: Parallel connection
Pr.08-07 determines the primary low pass filter time when in PID control. Setting a large time
constant may slow down the response rate of drive.
Output frequency of PID control will filter by primary low pass function. This function could filtering
a mix frequencies. A long primary low pass time means filter degree is high and vice versa.
Inappropriate setting of delay time may cause system error.
PI Control: controlled by the P action only, and thus, the deviation cannot be eliminated entirely. To
eliminate residual deviations, the P + I control will generally be utilized. And when the PI control is
utilized, it could eliminate the deviation incurred by the targeted value changes and the constant
external interferences. However, if the I action is excessively powerful, it will delay the responding
toward the swift variation. The P action could be used solely on the loading system that
possesses the integral components.
PD Control: when deviation occurred, the system will immediately generate some operation load
that is greater than the load generated single handedly by the D action to restrain the increment of
the deviation. If the deviation is small, the effectiveness of the P action will be decreasing as well.
The control objects include occasions with integral component loads, which are controlled by the
Chapter 12 Description of Parameter Settings|C2000 Series
12-129
Factory Setting:100.0
Factory Setting:100.0
Factory Setting: 0.00
Factory Setting: 0.0
Factory Setting: 0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents