Rated Power of Induction Motor 1(kW)

Settings 0~655.35 kW
It is used to set rated power of the motor 1. The factory setting is the power of the drive.

Rated Speed of Induction Motor 1 (rpm)

Settings 0~65535
It is used to set the rated speed of the motor and need to set according to the value indicated on
the motor nameplate.

Pole Number of Induction Motor 1

Settings 2~20
It is used to set the number of motor poles (must be an even number).
No-load Current of Induction Motor 1 (A)
Settings 0 to the factory setting in Pr.05-01
The factory setting is 40% X rated current.
Stator Resistance(Rs) of Induction Motor 1
Rotor Resistance(Rr) of Induction Motor 1
Settings 0~65.535Ω
Magnetizing Inductance(Lm) of Induction Motor 1
Stator inductance(Lx) of Induction Motor 1
Settings 0~6553.5mH
~
Reserved
Full-load Current of Induction Motor 2(A)
Settings 10~120%
This value should be set according to the rated frequency of the motor as indicated on the motor
Chapter 12 Description of Parameter Settings|C2000 Series
12-87
Factory Setting: #.##
Factory Setting:
1710(60Hz 4 poles)
1410(50Hz 4 poles)
Factory Setting: 4
Unit: Amper
Factory Setting: #.##
Factory Setting: #.###
Factory Setting: #.#
Unit: Amper
Factory Setting:#.##