Treatment for Encoder Feedback Fault

Settings 0: Warn and keep operating

Detection Time of Encoder Feedback Fault

Settings 0.0~10.0 sec
When encoder loss, encoder signal error, pulse signal setting error or signal error, if time exceeds
the detection time for encoder feedback fault (Pr.10-09), the encoder signal error will occur. Refer
to the Pr.10-08 for encoder feedback fault treatment.

Encoder Stall Level

Settings 0~120%
This parameter determines the maximum encoder feedback signal allowed before a fault occurs.
(Max. output frequency Pr.01-00 =100%)
Detection Time of Encoder Stall
Settings 0.0~2.0 sec

Treatment for Encoder Stall

Settings
When the motor frequency exceeds Pr.10-10 setting and detection time exceeds Pr.10-11, it will
operate as Pr.10-12 setting.
load
encoder is us ed
at load side
1: Warn and RAMP to stop
2: Warn and COAST to stop
0: No function
0: No function
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
PG
car d
Gear
Gear
B1 or B2
A1 or A2
gear ratio
ON = A2: B2
MI=48
OF F=A 1:B 1
12-152
D riv er
Motor
Factory Setting: 2
Factory Setting: 1.0
Factory Setting: 115
Factory Setting: 0.1
Factory Setting: 2