Delta C2000 series User Manual page 334

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Concept of PID control
1.
Proportional gain(P):
the output is proportional to input. With only proportional gain control,
a steady-state error.
2.
Integral time(I):
the controller output is proportional to the integral of the controller input. To eliminate the
steady-state error, an "integral part" needs to be added to the controller. The integral time
decides the relation between integral part and error. The integral part will be increased by
time even if the error is small. It gradually increases the controller output to eliminate the
error until it is 0. In this way a system can be stable without steady-state error by proportional
gain control and integral time control.
3.
Differential control(D):
the controller output is proportional to the differential of the controller input. During
elimination of the error, oscillation or instability may occur. The differential control can be
used to suppress these effects by acting before the error. That is, when the error is near 0,
the differential control should be 0. Proportional gain(P) + differential control(D) can be used
to improve the system state during PID adjustment.
When PID control is used in a constant pressure pump feedback application:
Set the application's constant pressure value (bar) to be the set point of PID control. The pressure
sensor will send the actual value as PID feedback value. After comparing the PID set point and
PID feedback, there will be an error. Thus, the PID controller needs to calculate the output by
using proportional gain(P), integral time(I) and differential time(D) to control the pump. It controls
the drive to have different pump speed and achieves constant pressure control by using a 4-20mA
signal corresponding to 0-10 bar as feedback to the drive.
no fuse breaker
(NFB)
R(L1)
S(L2)
T(L3)
1. Pr.00-04 is set to 10 (Display PID analog feedback signal value (b) (%))
2. Pr.01-12 Acceleration Time will be set as required
3. Pr.01-13 Deceleration Time will be set as required
4. Pr.00-21=0 to operate from the digital keypad
5. Pr.00-20=0, the set point is controlled by the digital keypad
6. Pr.08-00=1 (Negative PID feedback from analog input)
7. ACI analog input Pr. 03-01 set to 5, PID feedback signal.
Chapter 12 Description of Parameter Settings|C2000 Series
R(L1)
U(T1)
S(L2)
V(T2)
T(L3)
W(T 3)
F eedback 4-20mA
cor responds
0-10bar
ACI/A VI
(4- 20mA /0- 10V )
ACM
analog si gnal common
12-127
there will always be
water pump
IM
3~
throttle
pressure
sensor
DC
- +