Output Current Level Setting For Multi-Function Output Terminals; Output Boundary For Multi-Function Output Terminals; External Operation Control Selection After Reset And Activate - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

If this parameter is used without DC brake, it will be invalid. Refer to the following operation timing.
frequency
co mma nd
output
frequency
RUN/STOP
Multi-function output
(mec hani cal brake
relea se)
Pr.02-11 to 02-14=d12
me chanical brake

Output Current Level Setting for Multi-function Output Terminals

Settings
0~100%
When output current is higher or equal to Pr.02-33, it will activate multi-function output terminal
(Pr.02-13, 02-14, 02-16, and 02-17 is set to 27).
When output current is lower or equal to Pr.02-33, it will activate multi-function output terminal
(Pr.02-13, 02-14, 02-16, and 02-17 is set to 28).

Output Boundary for Multi-function Output Terminals

Settings 0.00~600.00Hz
When output frequency is higher or equal to Pr.02-34, it will activate the multi-function terminal
(Pr.02-13, 02-14, 02-16, 02-17 is set to 29).
When output frequency is lower
(Pr.02-13, 02-14, 02-16, 02-17 is set to 30).

External Operation Control Selection after Reset and Activate

Settings 0: Disable
1: Drive runs if the run command still exists after reset or re-boots.
Setting 1:
Status 1: After the drive is powered on and the external terminal for RUN keeps ON, the drive will
run.
Status 2: After clearing fault once a fault is detected and the external terminal for RUN keeps ON,
the drive can run after pressing RESET key.
Chapter 12 Description of Parameter Settings|C2000 Series
zero
speed
brake
or equal to
12-49
A
B=A
RUN
relea se
Pr.02-34, it will activate the multi-function terminal
ze ro
sp eed
STOP
brak e
Tim e
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 0