Feedback Signal Detection Time; Feedback Signal Fault Treatment; Sleep Time - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Feedback Signal Detection Time

Settings 0.0~3600.0 sec
Pr.08-08 is valid only if the feedback signal is ACI.
This parameter sets the detection time of abnormal PID derative. If detection time is set to 0.0,
detection function is disabled.

Feedback Signal Fault Treatment

Settings 0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
This parameter is valid only when the feedback signal is ACI.
AC motor drive acts when the feedback signals (analog PID feedback or PG (encoder) feedback)
are abnormal.
Sleep Frequency
Settings 0.00~600.00Hz
Wake-up Frequency
Settings 0.00~600.00Hz

Sleep Time

Settings 0.00~6000.0 sec
If the command frequency falls below the sleep frequency, for the specified time in Pr. 08-12, then
the drive will shut off the output and wait until the command frequency rises above Pr.08-11.
08-11
Wake-up frequency
08-10
Sleep frequency
PID Deviation Level
Settings 1.0~50.0%
PID Deviation Time
Settings 0.1~300.0 sec
Chapter 12 Description of Parameter Settings|C2000 Series
Frequency command
actual output frequency
sleep time
08-12
Sleep Function
12-131
Factory Setting: 0.0
Factory Setting: 0
Factory Setting: 0.00
Factory Setting: 0.00
Factory Setting: 0.0
0Hz
Factory Setting: 10.0