ω(rad/s) value= Pr.05-03。
Rev ers e mot or mode
06-1 2 current limit
Exte rnal ana lo g t ermin als
Pr. 03-00~02
7: positive to rque limit
10: pos itiv e/n egat iv e torque limit
9: regen erativ e t orque limit
Pr. 11-19
Reverse rege nerat ive
to rque limit
s peed
Pr. 11-20
Reverse mot or
to rque limit
Ex te rnal ana lo g t ermin als
Pr. 03-00~ 03-0 2
8: nega tiv e to rque limit
10: positive/n egat ive torque limit
06-1 2 current limit
Reverse mot or mode
Gain Value of Flux Weakening Curve for Motor 1
Settings 0~200%
Gain Value of Flux Weakening Curve for Motor 2
Settings 0~200%
Pr.11-21 and 11-22 are used to adjust the output voltage of flux weakening curve.
For the spindle application, the adjustment method is
1. It is used to adjust the output voltage when exceeding rated frequency.
2. Monitor the output voltage
3. Adjust Pr.11-21 (motor 1) or Pr.11-22 (motor 2) setting to make the output voltage reach motor
rated voltage.
4. The larger number it is set, the larger output voltage you will get.
Chapter 12 Description of Parameter Settings|C2000 Series
π
×
RPM
2
=
rad
/
s
60
Po sitiv e
to rque
E xt ernal an alog t erminals
7: po sitiv e t orque limit
10: pos itiv e/ne gativ e t orque limit
Pr. 11-17
Fo rwa rd moto r
t orque limit
Q uadr ant II
Q uadr ant I
Q uadr an t III Q ua dr an t IV
Pr. 11-18
Forward re genera tive
t orque limit
E xt ernal an alog t erminals
8 : ne gativ e t orque limit
10: pos itive/ne gativ e t orque limit
Nega tive
to rque
12-163
Forward mo tor mo de
06-1 2 current limit
P r. 03-00 ~02
The level o f t orque limit will b e
th e min. va lu e of fo llowing thre e v alues
speed
Pr. 03-00~03-02
06-1 2 c urrent limit
Forward mo tor mo de
Factory Setting: 90
Factory Setting: 90