Delta C2000 series User Manual page 320

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

Settings 0~64799 min
Pr.06-63 to Pr.06-68 are used to record the operation time for 6 malfunctions and it can also check
if there is any wrong with the drive according to the internal time.
When the malfunction occurs during operation, it records fault in Pr.06-17~06-22 and operation
time is recorded in Pr.06-63~06-68.
For example: When the first fault ovA occurs after operation 3000 min., second fault ovd occurs at
3482 min., third fault ovA occurs at 4051 min., fourth fault ocA at 5003 min., fifth fault ocA at 5824
min., sixth fault ocd occurs at 6402 min. and seven fault ocS at 6951 min..
It'll be recorded as the following table:
It will be recorded as the following table:
First fault
Second fault
Third fault
Seven fault
Time interval between errors occur (day)
Settings Read only
Time interval between errors occur (minute)
Settings Read only
Low Current Setting Level
Chapter 12 Description of Parameter Settings|C2000 Series
Pr.06-17
ovA
Pr.06-17
ovd
Pr.06-18
ovA
Pr.06-17
ovA
Pr.06-18
ovd
Pr.06-19
ovA
Pr.06-17
ocS
Pr.06-18
ocA
Pr.06-19
ocA
Pr.06-20
ovA
Pr.06-21
ovd
Pr.06-22
ovA
12-113
Factory Setting: Read only
Pr.06-63
3000 ovA occurs at the 3000 min
after operating.
Pr.06-63
3482
ovd occurs at 482 min after
last fault (ovA)
Pr.06-64
3000
Pr.06-63
4051
ovA occurs at 569 min after
last fault (ovd)
Pr.06-64
3482
Pr.06-65
3000
Pr.06-63
12
(12-5824)+64800=58988 min
ocS occurs at 58988 min after
last fault (ocA)
Pr.06-64
5824
Pr.06-65
5003
Pr.06-66
4051
Pr.06-67
3482
Pr.06-68
3000
Factory Setting: Read only
Factory Setting: Read only
Factory Setting: 0.0
3482-3000=482 min
4051-3482=569 min