Ladder diagram:
X0
Example
X1
Mnemonic

Parallel connection- B contact

ORI
X0~X17
Operand
The ORI command is used in the parallel connection of B contact. The function of the
command is to readout the status of present specific series connection contacts, and
then to perform the "OR" calculations with the logic calculation result before the
contacts, thereafter, saving the result into the accumulative register.
Ladder diagram:
Example
X0
X1
Mnemonic

Series connection (Multiple Circuits)

ANB
Operand
To perform the "ANB" calculation between the previous reserved logic results and
contents of the accumulative register.
Ladder diagram:
Example
X0
X2
Block A
Mnemonic

Parallel connection (Multiple circuits)

ORB
Operand
ORB is to perform the "OR" calculation between the previous reserved logic results
and contents of the accumulative register.
Y1
Y0~Y17
M0~M799
Y1
X1
ANB
Y1
X3
Block B
16-39
Chapter 16 PLC Function |C2000 Series
Command code: Operation:
LD
OR
OUT
Function
T0~159
Command code: Operation:
LD
X0
ORI
X1
OUT
Y1
Function
None
Command code: Operation:
LD
X0
ORI
X2
LDI
X1
OR
X3
ANB
OUT
Y1
Function
None
Load contact A of
X0
X0
Connect to contact
X1
A of X1 in parallel
Y1
Drive Y1 coil
C0~C79
D0~D399
Load contact A of X0
Connect to contact B of
X1 in parallel
Drive Y1 coil
Load contact A of X0
Connect to contact B of
X2 in parallel
Load contact B of X1
Connect to contact A of
X3 in parallel
Connect circuit block in
series
Drive Y1 coil