09 Communication Parameters
When using communication devices, connect AC
drive with PC by using Delta IFD6530 or IFD6500.
09-00
Communication Address
Settings
If RS-485 serial communication controls the AC motor drive, you must set the communication
address for this drive in this parameter. Each AC motor drive's communication address must be
different.
09-01
COM1 Transmission Speed
Settings
Sets the transmission speed of the computer and the drive.
Options are 4.8 Kbps, 9.6 Kbps, 19.2 Kbps, or 38.4 Kbps; otherwise, the transmission speed is
set to the default 9.6 Kbps.
09-02
COM1 Transmission Fault Treatment
Settings
Sets the response for Modbus communication errors in with the host. Set the detection time in
Pr.09-03.
When a transmission error occurs (for example, the error code CE10 is displayed), the error
remains even if the transmission status returns to normal, and does not clear automatically. In this
case, set a reset command (Reset) to clear the error.
09-03
COM1 Time-out Detection
Settings
Sets the communication time-out.
09-04
COM1 Communication Protocol
Settings
1–254
4.8–38.4 Kbps
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning, no fault, and continue operation
0.0–100.0 sec.
1: 7, N, 2 (ASCII)
2: 7, E, 1 (ASCII)
3: 7, O, 1 (ASCII)
12.1-09-1
Chapter 12 Description of Parameter SettingsME300
You can set this parameter during operation.
Default: 1
Default: 9.6
Default: 3
Default: 0.0
Default: 1