Output Setting For Frequency Division (Denominator) - Delta C2000 series User Manual

Classical field oriented. control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

2: Phase B leads in a forward run command and phase A leads in a reverse
run command
A
B
3: Phase A is a pulse input and phase B is a direction input. (L =reverse
direction, H=forward direction)
A
B
4: Phase A is a pulse input and phase B is a direction input. (L=forward
direction, H=reverse direction)
A
B
5: Single-phase input
A

Output Setting for Frequency Division (denominator)

Settings 1~255
This parameter is used to set the denominator for frequency division (for PG card EMC-PG01L or
EMC-PG01O). For example, when it is set to 2 with feedback 1024ppr, PG output will be
1024/2=512ppr.
Electrical Gear at Load Side A1
Electrical Gear at Motor Side B1
Electrical Gear at Load Side A2
Electrical Gear at Motor Side B2
Settings 1~65535
Parameters 10-04 to 10-07 can be used with the multi-function input terminal (set to 48) to switch
to Pr.10-04~10-05 or Pr.10-06~10-07 as shown as follows
Chapter 12 Description of Parameter Settings|C2000 Series
FWD
FWD
FWD
12-151
REV
REV
REV
Factory Setting: 1
Factory Setting: 100