Chapter 12 Description of Parameter Settings|C2000 Series
This parameter determines the frequency when DC Brake will begin during deceleration. When
this setting is less than start frequency (Pr.01-09), the start-point for DC brake will start from the
min. frequency.
DC Brake at Start-up is used for loads that may move before the AC drive starts, such as fans and
pumps. Under such circumstances, DC Brake can be used to hold the load in position before
setting it in motion.
DC Brake at stop is used to shorten the stopping time and also to hold a stopped load in position,
such as crane or cutting machine.
DC Brake at Start-up is used for loads that may move before the AC drive starts, such as fans and
pumps. Under such circumstances, DC Brake can be used to hold the load in position before
setting it in motion.
DC Brake at stop is used to shorten the stopping time and also to hold a stopped load in position,
such as crane or cutting machine.

Voltage Incrasing Gain

Settings 1~200%
When the user is using speed tracking, adjut Pr07-05 to slow down the increasing of voltage if
there are errors such as oL or ocv. Then the speed tracking time will be longer and the Pr07-09
Pivot Point of the Speed Tracking of the Current 20~200%, factory setting 50. If the pivot point of
the user is higher than the Pr06-03 pivot point of the oc stall, then the drive will choose the pivot
point of Pr06-03 as the highest pivot point of the speed tracking.

Restart after Momentary Power Loss

Settings 0: Stop operation
This parameter determines the operation mode when the AC motor drive restarts from a
momentary power loss.
The power connected to the drive may power off momentarily due to many reasons. This function
allows the drive to keep outputting after power is on again after power off and won't cause drive
stops.
Setting 1: Operation continues after momentary power loss, speed search starts with the Master
Frequency reference value after drive output frequency and motor rotator speed is synchronous.
Output frequen cy
01-09
Minimum
out put
frequen cy
Run /Stop
1: Speed search for last frequency command
2: Speed search for the minimum output frequency
DC Br ak Time
07-04
during St opping
Star t- point for
DC br ake
time during
stopping
OFF
ON
DC Brake Time
12-116
Time
Factory Setting: 100