From the table, we see that the PWM carrier frequency has a significant influence on the
electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise. Therefore, if the
surrounding noise is greater than the motor noise, lower the carrier frequency is good to reduce the
temperature rise. Although it is quiet operation in the higher carrier frequency, the entire wiring and
interference resistance should be considerate.
When the carrier frequency is higher than the factory setting, it needs to protect by decreasing the
carrier frequency. See Pr.06-55 for the related setting and details.
Reserved

PLC Command Mask

Bit 0: Control command by PLC force control
Settings
Bit 1: Frequency command by PLC force control
Bit 2: Position command by PLC force control
Bit 3: Torque command by PLC force control
This parameter determines if frequency command or control command is occupied by PLC
Source of the Master Frequency Command(AUTO)
0: Digital keypad
Settings
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
4: Pulse input without direction command (Pr.10-16 without direction)
5: Pulse input with direction command (Pr.10-16)
Chapter 12 Description of Parameter Settings|C2000 Series
460V Series
1-20HP [0.75-15kW]
02~15kHz
8kHz
Electromagnetic
Acoustic
Noise or Leakage
Noise
Significant
M inimal
Significant
12-12
25-75HP [18.5-55kW] 100-475HP [75-355kW]
02~10kHz
6kHz
2kHz
Heat
Dissipation
Current
Minimal
M inimal
Significant
Factory Setting: Read Only
02~09kHz
4kHz
Current
Wave
Factory Setting: 0